Chapter 3

Seismic Behavior of Masonry Structures

10 Hours · 14 Marks 6 Past Questions · 54 Marks

Syllabus & Marks Distribution

DetailInformation
CourseSeismic Resistant Design of Masonry Structures — ENCE 367 (Elective I)
Chapter3 — Seismic Behavior of Masonry Structures
Teaching Hours10 hours
Marks Allocation14 marks — the second largest chapter
Total Course Marks60 marks (final exam) · 45 teaching hours
Weight23.3% of the final paper
Related codesNBC 105, NBC 109, NBC 203, NBC 204, IS 1893, IS 4326, IS 13828

Syllabus Topics

  • 3.1  Basic concept of seismic effect in masonry structure; failure mechanism
  • 3.2  Historical buildings with seismic resisting features
  • 3.3  Lateral force resisting systems
  • 3.4  In-plane and out-of-plane behavior of walls
  • 3.5  Box-integrity-action of masonry structures
  • 3.6  Modes of failure of masonry structures
  • 3.7  Typical damages to masonry buildings in earthquakes
  • 3.8  Seismic performance due to various factors — geometrical and mass irregularities; opening size and location; eccentrically acting gravity load; eccentric lateral force; rigid and flexible floor diaphragm; slender wall; horizontal and vertical bands; material properties; construction quality
  • 3.9  Seismic performance of masonry buildings during past earthquakes
This is the chapter the examiner loves. “Failure mechanism of masonry buildings during earthquakes” has been asked in every single one of the last six papers, usually for 8–12 marks, and almost always with the instruction “with neat sketches” and “suggest mitigation measures”. Learn the sketches, not just the words.

Importance & Frequently Asked Topics VERY HIGH

Asked in 6 of the last 6 papers for a total of 54 marks — an average of 9 marks per paper, and the highest-yield theory chapter in the course. Together with Chapter 4 it carries 32 of the 60 final marks.

Marks Distribution by Each Exam

ExamMarksQuestion asked
2075 Chaitra10Q2 — modes of failure in brick masonry, sketches, for both static and earthquake load
2076 Chaitra10Q3a — failure mechanism of masonry structures and remedial measures
2078 Bhadra6Q1b — major failure mechanism during the Gorkha earthquake, with sketch
2079 Bhadra8Q2b — in-plane vs out-of-plane behaviour + failure modes with neat sketch
2080 Bhadra12Q1b — failure mechanism during earthquake + mitigation measures, with sketches
2081 Bhadra8Q2a — failure mechanisms of stone-in-mud masonry in the 2080 Jajarkot earthquake

Frequently Asked Topics

TopicTimes AskedFrequency
Failure mechanism / modes of failure of masonry (with sketches)6
Mitigation / remedial measures to make masonry earthquake resistant2
In-plane vs out-of-plane behaviour1
Damage in a specific Nepali earthquake (Gorkha 2015, Jajarkot 2080)2
Failure under static vs earthquake load1
Box action, diaphragm rigidity, effect of openingsindirect

Topic-wise Importance & Exam Tips

TopicImportanceKey Points / Exam Tips
Modes of failure — in-planeHighFour modes: rocking, sliding, diagonal shear (bed-joint sliding / diagonal tension), toe crushing. Sketch each. State the giveaway: stair-stepped crack through the joints = weak mortar; straight X crack through the bricks = strong mortar.
Modes of failure — out-of-planeHighFour mechanisms: simple overturning, composed overturning, vertical flexure, horizontal flexure. Mention that h/t ratio and vertical precompression are the governing variables.
Typical earthquake damage patternsHighThe seven-item list: out-of-plane failure, in-plane shear/flexure, separation at junctions, failure of piers between openings, local failure, buckling/delamination, separation of roof from walls. Add corner separation and gable failure.
Mitigation / remedial measuresHighTwo papers demanded this explicitly. Answer with the bands + vertical bars + corner interlocking + diaphragm + opening rules checklist, keyed to the failure it prevents.
In-plane vs out-of-plane behaviourHighAnswer as a comparison table, then a sketch showing the same wall in both roles. Emphasise that every wall plays both roles as the shaking direction reverses.
Box action / box integrityMediumUse the four-wall (A1, A2, B1, B2) argument: the weak-direction wall pulls and pushes the strong-direction walls, so corner interlocking and bands are essential.
Effect of openings and irregularityMedium“Small, central, aligned, away from corners”. Quote the NBC/IS limits on opening size and the 600 mm corner distance.
Rigid vs flexible diaphragmMediumRigid → distributes in proportion to stiffness and can transmit torsion; flexible → distributes in proportion to tributary area and cannot transmit torsion. This is directly re-used in Chapter 4.
Failure under static loadMedium2075 asked for both. Static: vertical splitting under compression, crushing, buckling, settlement cracks, tensile/flexural cracks. Keep them separate from the seismic modes.
Historical buildings with seismic resisting featuresLowNot yet asked but explicitly in the new syllabus. Timber lacing (dhajji-dewari, taq), through-stones, timber bands, symmetric plan, small openings.

3.1  Basic Concept of Seismic Effect in Masonry Structures; Failure Mechanism

3.1.1  How do masonry houses behave during earthquakes?

Masonry buildings are brittle structures and are one of the most vulnerable of the entire building stock under strong earthquake shaking. The very large number of human fatalities in such buildings in past Nepali earthquakes is the direct consequence. Improving their seismic behaviour is therefore the central purpose of this course.

  1. Ground vibration during an earthquake causes inertia forces at the locations of mass in the building — principally at the roof and floor levels and in the walls themselves.
  2. These forces travel through the roof and walls to the foundation. The whole emphasis of earthquake-resistant design is to ensure that they reach the ground without causing major damage or collapse.
  3. Of the three components of a masonry building — roof, wall and foundation — the walls are the most vulnerable to the horizontal force.
  4. A wall topples easily if pushed horizontally at the top in a direction perpendicular to its plane (its weak direction) but offers much greater resistance if pushed along its length (its strong direction).
  5. The ground shakes simultaneously in the vertical (Z) and two horizontal (X, Y) directions, but the horizontal vibrations are the most damaging to normal masonry buildings.
  6. If all the walls are not tied together like a box, the walls loaded in their weak direction simply topple. If they are, the weak-direction walls can take advantage of the good lateral resistance offered by the walls loaded in their strong direction. The walls must also be tied to the roof and to the foundation to preserve overall integrity.
Diagram of the basic components of a masonry building - roof, wall and foundation - and a wall being pushed in its weak direction perpendicular to its plane and in its strong direction along its length
Fig. 3.1 The three components of a masonry building, and the difference between the weak direction (perpendicular to the wall plane) and the strong direction (along the wall length). Source: course lecture slides, IOE Pulchowk Campus.

3.1.2  Shear walls and cross walls

When the dominant ground motion is along one axis of the building:

• walls parallel to the direction of ground motion are called shear walls — they resist the force in-plane;
• walls orthogonal to it are called cross walls — they are loaded out-of-plane and also stiffen the shear walls at their ends.
Three-part diagram of a simple masonry building showing the applied lateral load in isometric view, the out-of-plane response of the transverse walls and the in-plane response of the shear walls
Fig. 3.2 A simple masonry building under lateral load: (a) the earthquake force applied to the whole building; (b) walls perpendicular to the shaking bend out-of-plane; (c) walls parallel to the shaking resist the force in-plane as shear walls. Source: course lecture slides, IOE Pulchowk Campus.

3.1.3  Concepts for earthquake resistant masonry

The basic principles of design and detailing in the codes are intentionally simple and easy to adopt. They focus on just two things:

1. Achieving strength and ductile behaviour
2. Maintaining structural integrity

The primary requirement is therefore the prevention of catastrophic collapse of the building or its components — and to achieve it in a relatively simple and cost-effective manner.

The concept of “acceptable risk”

Level of shakingPerformance objective
Minor earthquakeResist without damage.
Moderate earthquakeResist without significant structural damage, but some non-structural damage is accepted.
Major (severe) earthquakeResist without major failure of the structural framework — to prevent loss of life and to allow safe escape for the occupants.

Certain critical structures — hospitals, power generating units, communication centres — must be designed to remain operational during and after an earthquake.

Unreinforced masonry buildings are very common in rural and semi-urban Nepal, built from adobe, stone, burnt brick, concrete block and stabilised mud block, with mud, lime, cement or composite mortar. Normally they are designed — if at all — only for vertical loads, and because masonry has adequate compressive strength the structure behaves well as long as the loads remain vertical. It is the horizontal load that destroys it.

3.1.4  The three basic failure mechanisms of a masonry wall

Magenes and Calvi (1997) reduced the in-plane seismic behaviour of a masonry wall to three principal mechanisms. Every in-plane failure observed in the field is one of these, or a combination:

MechanismWhat happensGoverned by
(a) Shear crackingA diagonal crack forms across the panel, either stepping through the joints or running straight through the units.Mortar/unit strength, level of vertical precompression, aspect ratio
(b) SlidingThe wall slides horizontally along a bed joint, usually near the base or at sill level.Cohesion and friction of the bed joint, low precompression
(c) RockingThe wall or pier lifts off at one edge and rotates about its compressed toe as a rigid block, eventually crushing the toe.Slender (tall, narrow) piers with low vertical load
Three diagrams of a brick wall panel showing (a) a stepped diagonal crack, (b) horizontal sliding of the upper part on a bed joint and (c) rocking of the whole panel about its toe
Fig. 3.3 Principal failure mechanisms of masonry walls under seismic action (Magenes & Calvi, 1997): (a) shear/diagonal cracking, (b) sliding, (c) rocking failure. Source: course lecture slides, IOE Pulchowk Campus.

3.2  Historical Buildings with Seismic Resisting Features

Long before any code existed, builders in seismic regions arrived empirically at features that improve performance. Recognising them matters because (a) they explain why some historic buildings survived 1934 and 2015, and (b) they are the ancestors of the modern band-and-tie system.

Traditional featureWhat it does
Timber lacing / horizontal timber bands — dhajji-dewari and taq of Kashmir, timber bands in Newari and Bhutanese constructionActs exactly as a modern lintel or roof band: ties the walls together, gives horizontal bending strength, and stops a crack from running through the full wall height. Timber's ductility absorbs energy.
Timber-braced infill frames (dhajji-dewari = “patchwork quilt wall”)Small masonry panels confined by a timber frame — the historic ancestor of confined masonry. Damage is contained within each small panel.
Through stones / bond stones at regular spacingTies the two leaves of a thick stone wall together and prevents delamination — the single most effective measure for random rubble masonry.
Good corner interlocking and quoin stonesPrevents corner separation, the first damage to appear.
Symmetric, compact, rectangular plan; low heightAvoids torsion and limits the inertia force; most surviving temples and pati are low and squat.
Thick walls with a low height-to-thickness ratio; walls tapering with heightHigh out-of-plane stability and a lower centre of mass.
Small, few and centrally placed openingsKeeps the shear walls solid and the piers wide.
Light roofs on the upper storeysReduces the inertia force where it does the most damage.
Wide plinth / stepped foundation on firm groundReduces differential settlement and rocking.
Buttresses, pilasters and closely spaced cross wallsReduce the effective length and slenderness of long walls (Chapter 2, §2.6.4).
The Nepali paradox. Traditional Kathmandu Valley buildings combine good features (symmetry, timber floors and bands, thick walls, quality dachi appa facing brick) with fatal ones (three-leaf walls with a weak rubble-and-mud core, no through-bonding between the leaves, unanchored timber joists giving no diaphragm action, heavy roofs, and very large ground-floor shop openings). Which set dominates decides whether the building survives.

3.3  Lateral Force Resisting Systems

3.3.1  The load distribution system

A building is subjected to two families of load:

All walls in general can carry vertical load, but the ability of a wall to carry lateral load depends entirely on its disposition relative to the direction of that load. The chain is:

Lateral load on the face (facade) wall  →  floors and roof acting as horizontal beams (diaphragms)  →  cross walls acting as shear walls  →  foundation  →  ground.

The strength and stiffness of the floors as horizontal girders is vital; roofs and floors of lightweight construction must therefore be used with care. A structure must have adequate stability in the direction of both principal axes — so-called “cross-wall” construction may have very little lateral resistance in the longitudinal direction. In multi-storey buildings a cellular or box-type layout is desirable for both stability and economy.

The size, shape and location of openings in the external walls has considerable influence on stability and on the magnitude of the stresses due to lateral load. If the openings in the longitudinal walls are placed so that portions of those walls act as flanges to the cross walls, the strength of the cross walls is considerably increased and the structure becomes much more stable — the flange-and-web action confirmed by shaking-table tests, in which walls A act as flanges to wall B acting as the web.

Ordinarily a load-bearing masonry structure is designed for permissible compressive and shear stresses (with no tension) as a vertical cantilever. No moment transfer is allowed for at the floor-to-wall connections, and the lateral forces are assumed to be resisted by diaphragm action of the floor/roof slabs, which, acting as horizontal beams, transmit the lateral force to the cross walls in proportion to their relative stiffness (moment of inertia).

3.3.2  Design loads and load combinations

ItemProvision
Loads to be consideredDead loads of walls, columns, floors and roofs; live loads of floors and roof; seismic forces; wind loads on walls and sloping roofs. Other loads such as vibration from railways or machinery are added by engineering judgement.
Dead loadsCalculated from unit weights taken in accordance with IS 875 (Part 1).
Design loads generallyIn accordance with IS 875 (1987).
Seismic loadsDetermined in accordance with IS 1893 (Part 1) — or NBC 105 in Nepal.
During constructionSuitable measures must ensure the partly-built masonry is not damaged by seismic/wind force, backfill behind walls or temporary construction loads.
Load combinations (allowable stress design, IS 1905):
• DL + IL   • DL + IL + (WL or EL)   • DL + (WL or EL)   • 0.9 DL + (WL or EL)

For wind and earthquake, the reversal of forces must be considered. The structure is designed for the critical stresses resulting from these combinations.
Permissible stresses. Permissible stresses and loads may be increased by one-third for the combinations that include wind or earthquake.

Equivalently — and this is the form usually used in the exam — keep the full permissible stress and apply a 25% reduced load:
• 0.75 [DL + IL + (WL or EL)]   • 0.75 [DL + WL]   • 0.75 [0.9 DL + EL]

3.3.3  Lateral load distribution — rigid and flexible diaphragms

Lateral loads from earthquake or wind are generally considered to act along the principal axes of the building. How they are shared out among the walls depends on the rigidity of the horizontal diaphragm and of the walls themselves.

BasisRigid diaphragmFlexible diaphragm
DefinitionDoes not undergo significant in-plane deformation relative to the supporting wallsChanges shape when subjected to lateral load
Typical constructionRC slab, in-situ concrete floorTimber joists with plank flooring, CGI sheet roof, unbraced trusses, jack-arch floor
Distribution of storey shearIn proportion to the relative stiffness (rigidity) of the wall elementsIn proportion to the tributary area associated with each wall, exactly as for vertical load
TorsionCan transmit torsional moment; horizontal torsion arises from the eccentricity between the centre of mass and the centre of rigidity, and induces forces in walls both parallel and perpendicular to the load directionCannot transmit torsional forces
Support to out-of-plane wallsProvides a firm horizontal support at the top of the wallGives little or no support — the out-of-plane wall spans the full storey height unaided
AnalysisIn-plane rigidities include both shearing and flexural deformation; rigidity of walls perpendicular to the load is usually disregarded, except for the stiffening (flange) effect where the connection is adequateSimple tributary-area statics
Seismic performanceMuch better — true box actionPoor — walls act individually and out-of-plane collapse dominates
Isometric and plan diagrams comparing how a flexible diaphragm distributes storey shear by tributary width and how a rigid diaphragm distributes it in proportion to wall area or stiffness
Fig. 3.4 Distribution of lateral load in buildings with (a) flexible and (b) rigid diaphragms. With a flexible diaphragm each wall takes the shear from its own tributary width (V/4, V/2, V/4); with a rigid diaphragm each wall takes a share proportional to its own stiffness (Ai/ΣA). Source: course lecture slides, IOE Pulchowk Campus.

3.3.4  Elements of the lateral load resisting system

The elements that actually resist lateral load in a masonry building are:

3.4  In-plane and Out-of-plane Behaviour of Walls 2079 Bhadra, Q2b

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. Differentiate between in-plane and out-of-plane behaviour of masonry structures. Explain the different failure modes of masonry structures with a neat sketch. [8] (2079 Bhadra, Q2b)
BasisIn-plane behaviourOut-of-plane behaviour
Direction of loadForce acts parallel to the plane of the wall (along its length)Force acts perpendicular to the plane of the wall
Name of the wallShear wall — the “strong direction”Cross wall / transverse wall — the “weak direction”
Structural actionDeep cantilever / coupled piers — carries the storey shear by in-plane shear and in-plane bendingVertical slab or plate spanning between floor and roof, and horizontally between cross walls
Governing stressDiagonal tension, bed-joint shear, toe compressionFlexural tension normal to the bed joints — the weakest property of masonry
Stiffness & strengthHigh — a wall is one or two orders of magnitude stiffer in-planeVery low
Governing parametersAspect ratio L/heff, level of vertical precompression, mortar and unit strength, size and position of openingsHeight-to-thickness (h/t) ratio and the vertical stress on the wall; also the span between cross walls
Typical failure modesRocking, sliding, diagonal shear (bed-joint sliding or diagonal tension), toe crushing — the X crackSimple overturning, composed overturning, vertical flexure, horizontal flexure — the wall falls outward
Consequence of failureSevere cracking, loss of stiffness, but the wall usually stays standingCollapse — the wall falls out, the floor/roof loses its support and pancakes. The dominant killer.
What controls itWall area (density of walls), pier proportionsBands, cross walls, wall anchorage, diaphragm rigidity, wall slenderness
The key sentence for the exam: because the earthquake shakes the building in both horizontal directions and reverses every fraction of a second, every wall is an in-plane wall at one instant and an out-of-plane wall the next. A wall is only safe if it is adequate in both roles — and it is the out-of-plane role that governs.
Three diagrams of an unreinforced masonry wall showing its deformation under vertical loads only, under horizontal loads only, and under combined vertical and horizontal loads
Fig. 3.5 Behaviour of an unreinforced masonry wall under vertical load, under out-of-plane horizontal load, and under the two combined. Vertical precompression is what keeps the wall stable; when it is low (upper storeys, gables) the wall is far more vulnerable. Source: course lecture slides, IOE Pulchowk Campus.

3.5  Box Integrity Action of Masonry Structures

Box action is the behaviour in which the roof, the walls and the foundation of a masonry building act together as a single closed box rather than as a set of independent panels, so that the weak (out-of-plane) walls are supported by the strong (in-plane) walls, and the whole building moves as one unit.

3.5.1  Why it is needed — the four-wall argument

Consider the four-wall system of a single-storey masonry building, with walls A1, A2 (say the long walls) and B1, B2 (the short walls). For shaking in the direction shown:

  1. Inertia forces act in the strong direction of some walls and the weak direction of others.
  2. Walls shaken in their weak direction seek support from the other walls — B1 and B2 seek support from A1 and A2.
  3. More precisely, wall B1 pulls walls A1 and A2, while wall B2 pushes against them.
  4. At the next instant the shaking direction reverses, and a moment later it acts along the perpendicular horizontal axis — now A and B swap roles: B1 and B2 become the strong walls and A1 and A2 the weak ones.
  5. Thus walls transfer load to each other at their junctions, and through the lintel bands and the roof. Hence the masonry courses of the walls meeting at a corner must have good interlocking, and openings near wall corners are detrimental to good seismic performance.
(a) NO box action — walls act alone roof drops in Weak-direction wall overturns and falls out Roof loses its support → collapse (b) BOX action — walls act as one Rigid diaphragm Lintel band B1 (weak dir.) A (strong dir.) B1 pulls / B2 pushes wall A at the interlocked corners Weak wall supported by the strong walls Building oscillates as one rigid box Direction of shaking
Fig. 3.6 Box action. Without it (a) the wall loaded in its weak direction overturns and the roof loses its support; with it (b) the corner interlocking, the bands and the rigid diaphragm let the weak wall hang on to the strong walls and the whole building moves as one.

3.5.2  Requirements for good box action

RequirementHow it is achieved
Wall-to-wall connectionToothed or stepped vertical joints at all corners and T-junctions (build corners first to 600 mm, or tooth in 450 mm lifts); vertical containment reinforcement at junctions.
Wall-to-roof / floor connectionRoof band at eave level and positive metal anchors so that the diaphragm can actually deliver force to the walls. A loosely connected roof is a threat to good seismic behaviour.
Wall-to-foundation connectionPlinth band, especially where the soil is soft or uneven.
A stiff diaphragmRC slab, or a timber floor stiffened with diagonal bracing/plywood sheathing.
Horizontal bands at all levelsPlinth, sill, lintel, roof and gable bands — a lintel band alone ties the walls together and makes them behave as a single unit.
Walls not unduly slenderLimit h/t; provide cross walls or buttresses to reduce the span of long walls. Unduly slender walls are a threat to good seismic behaviour.
Simple, symmetric configurationCompact rectangular plan, uniform mass and stiffness distribution.

3.5.3  Configuration rules that support box action

3.6  Modes of Failure of Masonry Structures 2075 Chaitra2076 Chaitra2079 Bhadra2080 Bhadra

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. Explain different modes of failure in brick masonry structures with sketches for both static and earthquake load. [10] (2075 Chaitra, Q2)
  2. Discuss in brief failure mechanism of masonry structures and remedial measures. [10] (2076 Chaitra, Q3a)
  3. Differentiate between in-plane and out-of-plane behaviour... Explain the different failure modes of masonry structures with a neat sketch. [8] (2079 Bhadra, Q2b)
  4. Describe failure mechanism of masonry building during earthquake and suggest its mitigation measures to make earthquake resistant with sketches. [12] (2080 Bhadra, Q1b)

3.6.1  The standard seven-fold classification

The failure pattern of masonry structures during an earthquake is classified as:

  1. Out-of-plane flexural and/or out-of-plane shear failure
  2. In-plane shear and/or in-plane flexural failure
  3. Separation of walls at junctions (corner separation)
  4. Failure of masonry piers between openings
  5. Local failures (parapets, gables, chimneys, cornices, projections)
  6. Buckling / delamination of walls and piers
  7. Separation of the roof from the walls

3.6.2  Failure under static (gravity) load 2075 Chaitra, Q2

The 2075 paper asked for failure modes under both static and earthquake load, so keep the two lists distinct. Under pure vertical (static) load a masonry wall or pier can fail by:

Static failure modeDescription & cause
Compression failure by vertical splittingThe characteristic mode. The soft mortar bulges laterally, is restrained by the units, and puts the units into lateral tension, so vertical cracks split through the bricks (Chapter 2, Fig. 2.8). Occurs in short, stocky walls with low slenderness.
Local crushing / bearing failureUnder a concentrated load from a beam or lintel bearing, where the stress exceeds the local capacity.
Buckling (lateral instability)In slender walls and piers — high slenderness ratio; failure occurs at a stress far below the crushing strength (Chapter 2, Fig. 2.16).
Flexural tension cracking due to eccentric loadWhen the resultant falls outside the middle third (e > t/6), tension develops on one face and a horizontal crack opens along a bed joint.
Cracking due to differential settlementDiagonal tension cracks running towards the settling support — doming (heaving of expansive soil at the centre) gives cracks sloping one way and dishing (shrinkage at the centre) the other.
Shrinkage / thermal / moisture movement cracksVertical cracks in long unjointed walls; horizontal cracks under a concrete slab that shrinks.
Sliding at a damp-proof courseWhere the DPC breaks the bond and lateral thrust exists.
Arch thrust / spreadingHorizontal thrust from an arch, vault or sloping roof pushes the supporting wall outward.

3.6.3  In-plane failure modes under earthquake load

Four modes, distinguished by the aspect ratio of the pier, the vertical precompression and the relative strength of unit and mortar:

ModeMechanismWhen it occursCrack appearance
1. Rocking (flexural) A horizontal flexural crack opens at the heel of the pier; the pier then rotates as a rigid block about its compressed toe. Slender piers (tall relative to their length) with low vertical load. Horizontal cracks at top and bottom of the pier; crushing at the toes. Relatively ductile and not immediately dangerous.
2. Sliding (bed-joint shear) The wall slides horizontally along a bed joint when the shear exceeds the cohesion plus friction. Low vertical load and weak mortar; commonly at the base, at sill level or at a DPC. A single horizontal crack with visible offset. Often stair-stepped where head joints open and close to allow movement on the bed joints.
3. Diagonal shear — bed-joint sliding (stepped crack) The diagonal crack follows the mortar joints, stepping from bed joint to head joint. Weak mortar, strong units — the joint is the weak link. The usual case in Nepali brick-in-mud and stone-in-mud masonry. A stair-stepped diagonal crack through the joints, with the bricks intact.
4. Diagonal tension (X cracking) and toe crushing Principal tensile stress exceeds the tensile strength of the masonry as a whole and the crack runs straight through the units. Under reversed cycles two crossing cracks form. Strong mortar, weak units and high compressive stress; squat piers. The classic straight “X” crack cutting through the bricks, followed by spalling and crushing of the toes.
The one-line diagnostic that earns marks: a stair-stepped crack that runs around the bricks means the mortar was weaker than the units; a straight diagonal crack that runs through the bricks means the mortar was stronger than the units and the compressive stress was high.
Diagrams of a masonry pier failing in flexure with horizontal cracks at top and bottom and in rocking about its toe
Fig. 3.7a In-plane failure modes — flexure and rocking. Source: course lecture slides.
Diagrams of a masonry pier failing by horizontal sliding on a bed joint and by diagonal shear cracking
Fig. 3.7b In-plane failure modes — sliding and diagonal shear. Source: course lecture slides.
Photograph of a masonry pier showing horizontal cracks at the top and bottom characteristic of rocking failure
Fig. 3.8a Rocking of piers — horizontal cracks top and bottom. Source: course lecture slides.
Photograph of a masonry pier between windows with crossing diagonal X cracks
Fig. 3.8b X-cracking of piers — diagonal tension under load reversal. Source: course lecture slides.
Photograph of a masonry wall that has slid horizontally along a bed joint at sill level
Fig. 3.8c Horizontal sliding along a bed joint. Source: course lecture slides.
Laboratory photograph of a brick masonry panel with strong mortar showing a straight diagonal crack passing through the bricks
Fig. 3.9a Diagonal tension with strong mortar — the crack cuts straight through the units.Source: course lecture slides.
Laboratory photograph of a brick masonry panel with weak mortar showing a stair-stepped crack following the mortar joints
Fig. 3.9b Diagonal tension with weak mortar — the crack steps around the units along the joints.Source: course lecture slides.

Progressive damage sequence of a squat pier (laboratory observation)

For a relatively short wall with L/heff of about 1.7, in which bed-joint sliding and toe-crushing capacities are similar, the moderately ductile sequence is:

  1. Flexural cracking at the heel of the wall.
  2. Diagonally oriented cracks at the toe, typically with spalling and crushing of the units.
  3. Sliding along a horizontal bed joint near the base, sometimes with stair-stepped bed-joint sliding higher up.
  4. With repeated cycles the diagonal cracks grow, and finally crushing of the toes or excessive sliding causes failure.

For stockier walls with L/heff > 1.25 the sequence is: flexural cracking at the base that does not propagate all the way across (giving a series of horizontal cracks above the heel) → sliding on bed joints in the central portion of the pier → diagonal cracks at the toe → large cracks at the upper corners.

Three sketches of a wall panel showing insignificant, moderate and heavy crack damage patterns
Fig. 3.10 Progressive in-plane crack damage in a wall panel — insignificant, moderate and heavy damage.Source: course lecture slides.

3.6.4  Out-of-plane failure modes (collapse mechanisms)

Out-of-plane failure occurs because of the lack of adequate wall ties, bands or cross walls. One common form is a rigid-body rocking motion occurring at three locations — at the top of the wall, at the bottom, and at mid-height. The important variables are the vertical stress on the wall and its height-to-thickness ratio; therefore walls at the top of buildings and slender walls are the most likely to suffer damage. In long walls without cross walls the failure mode is out-of-plane bending in the horizontal direction.

MechanismDescriptionCause
Simple overturningThe whole facade wall rotates outwards about its base as a single rigid block and falls away from the building.No connection at all between the facade and the transverse walls or the floor; the most common and most lethal mechanism.
Composed (compound) overturningThe facade overturns dragging with it a wedge-shaped portion of the adjoining transverse walls.Good interlocking at the corners but no floor/roof tie — the corner holds so the failure surface cuts diagonally into the return walls.
Vertical flexure (vertical bending)The wall is restrained at floor and roof level but bulges and hinges at mid-height, breaking into an upper and a lower part.Wall restrained top and bottom but too slender (high h/t); typical of upper storeys.
Horizontal flexure (horizontal bending / arching)The wall spans horizontally between cross walls or buttresses and fails with a vertical crack at mid-span and cracks at the supports.Long wall well tied at its ends but unsupported at the top — flexible diaphragm.
Gable-end failureThe triangular gable, which has little vertical load and no restraint at the top, topples and pulls the top of the end wall down with it.Missing gable band; missing attachment to the attic or ceiling.
Parapet / chimney failureA vertical cantilever with almost no precompression — falls into the street.Limiting SR for a free-standing wall is only 10.
Diagram and photographs of the simple overturning mechanism where a facade wall rotates outward about its base
Fig. 3.11a Simple overturning mechanism.Source: course lecture slides.
Diagram and photographs of the composed overturning mechanism where the facade drags a wedge of the return walls with it
Fig. 3.11b Composed overturning mechanism.Source: course lecture slides.
Diagram and photographs of the vertical flexure mechanism where a wall restrained top and bottom hinges at mid-height
Fig. 3.11c Vertical flexure mechanism.Source: course lecture slides.
Diagram and photographs of the horizontal flexure mechanism where a wall spanning between cross walls cracks vertically at mid-span
Fig. 3.11d Horizontal flexure mechanism.Source: course lecture slides.
Two isometric diagrams comparing out-of-plane failure of a confined masonry wall with a rigid RC slab diaphragm and with a flexible diaphragm
Fig. 3.12 Out-of-plane failure mechanisms of confined masonry walls: (a) with a rigid diaphragm the wall spans in two directions and fails with a diagonal (yield-line) pattern; (b) with a flexible diaphragm the wall spans only horizontally between transverse walls and is far more vulnerable.Source: course lecture slides, IOE Pulchowk Campus.

3.7  Typical Damages to Masonry Buildings in Earthquakes 2078 Bhadra2080 Bhadra2081 Bhadra

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. Discuss the failure mechanisms of the stone masonry buildings with mud mortar during the 2080 Jajarkot earthquake. [8] (2081 Bhadra, Q2a)
  2. Describe failure mechanism of masonry building during earthquake and suggest its mitigation measures to make earthquake resistant with sketches. [12] (2080 Bhadra, Q1b)
  3. Describe in brief with sketch major failure mechanism of masonry building during Gorkha earthquake. [6] (2078 Bhadra, Q1b)

3.7.1  Corner separation

Two photographs of earthquake damaged masonry buildings showing vertical separation cracks at the junction of two orthogonal walls
Fig. 3.13 Corner separation — vertical cracking and separation at the junction of two orthogonal walls.Source: course lecture slides, IOE Pulchowk Campus.

3.7.2  Out-of-plane failure and gable collapse

Photograph of a masonry building whose facade wall has fallen outward leaving the floors exposed
Fig. 3.14a Out-of-plane collapse of a facade wall.Source: course lecture slides.
Photograph of a stone masonry house where the gable end has toppled and pulled the top of the end wall and the roof down with it
Fig. 3.14b The gable pulls down the top of the end wall when the attachment to the attic or ceiling is missing.Source: course lecture slides.

3.7.3  Delamination of multi-leaf walls

Delamination — separation of the two (or three) wythes of a masonry wall through its thickness — is another major damage type. The outer leaf buckles and peels away, leaving the wall with a fraction of its original thickness and no capacity. It is the characteristic failure of random rubble stone walls with a weak inner core and no through-stones, and was the dominant mechanism in the 2080 Jajarkot earthquake.

Two photographs of stone masonry walls whose outer leaf has peeled away from the inner core, exposing the loose rubble fill
Fig. 3.15 Delamination of the wythes of a stone masonry wall, exposing the weak rubble core. Source: course lecture slides, IOE Pulchowk Campus.

3.7.4  Roof failure and other damage

Photograph of a masonry building where the roof has slid off and collapsed after the supporting walls failed
Fig. 3.16 Roof failure — an unanchored roof slides off the wall, or collapses when its supporting wall fails out-of-plane.Source: course lecture slides.

3.7.5  Damage grade classification (EMS)

Post-earthquake assessment uses the five damage grades of the European Macroseismic Scale. The basic steps of a detailed evaluation are: survey the building from outside → identify the cracks → examine the site for geotechnical hazard → inspect from inside → inspect at critical locations → interpret.

GradeExtent of damageSuggested post-earthquake action
G1 Negligible to slight
(no structural, slight non-structural)
Thin cracks in plaster; falling of plaster bits in limited parts; in rare cases fall of loose stone from the upper part of the building.Building need not be vacated; architectural repairs needed; seismic strengthening advised.
G2 Moderate
(slight structural, moderate non-structural)
Thin cracks in many walls; falling of plaster in large areas; damage to non-structural parts such as chimneys and projecting cornices. Load carrying capacity not reduced.Architectural repairs needed; seismic strengthening advised.
G3 Substantial to heavy
(moderate structural, heavy non-structural)
Large and extensive cracks in most walls; roof tiles detach; tilting or falling of chimneys; failure of individual non-structural elements such as partition or gable walls. Load carrying capacity partially reduced.Cracks in walls need grouting; architectural repairs required; seismic strengthening advised.
G4 Very heavy
(heavy structural, very heavy non-structural)
Gaps occur in walls; parts of walls collapse; partial structural failure of floors and roof; the building takes a permanent tilt.Vacate the building; demolish and reconstruct, or carry out extensive restoration.
G5 Destruction
(very heavy structural damage)
Total or near-total collapse.Vacate and demolish.
Line sketches of a masonry building showing progressively increasing damage from grade 3 through grade 4 to grade 5 destruction
Fig. 3.17 EMS damage grade identification sketches. Source: course lecture slides, IOE Pulchowk Campus.

3.7.6  Mitigation and Remedial Measures 2076 Chaitra, Q3a2080 Bhadra, Q1b

Two papers asked for the mitigation measures explicitly. Present them keyed to the failure they prevent — that structure alone earns marks:

Failure it preventsMeasure
Corner separationToothed / stepped joints at corners and T-junctions (corners built first to 600 mm, or toothing in 450 mm lifts); vertical containment reinforcement at all corners and junctions, anchored into the bands.
Out-of-plane collapseHorizontal bands at plinth, sill, lintel, roof and gable level; cross walls or buttresses to reduce the wall span; limit the height-to-thickness ratio; anchor the wall to the diaphragm.
Roof / floor separationPositive metal anchors tying the roof and floor to the walls; a roof band at eave level.
Loss of box actionProvide a rigid diaphragm (RC slab), or brace a timber floor with diagonals or plywood sheathing.
Delamination of stone wallsThrough-stones (bond stones) at regular spacing in both directions; or a substitute such as an S-shaped tie, a wooden dowel or a concrete bond block.
Diagonal shear cracking of piersUse good-quality mortar (never mud) matched to the unit; keep piers wide; limit and align the openings; provide bands above and below the openings.
Failure of piers between openingsOpenings small, few, centrally placed and vertically aligned, kept at least 600 mm (or half the wall height) from the corner; total opening length limited to about 50% of the wall length; provide vertical bars at the jambs.
TorsionSymmetric plan and uniform distribution of walls; separate irregular plans into simple rectangular blocks with a seismic gap.
PoundingAdequate seismic separation gap between adjacent blocks and buildings; separate the staircase tower.
Excessive inertia forceUse a light roof; limit the number of storeys (NBC 202 limits load-bearing masonry to about 3 storeys); reduce the mass of the upper floors.
Local / non-structural failureAvoid or reinforce parapets, gables, chimneys and heavy projections; provide a gable band or replace the gable with a light truss.
Poor materials / workmanshipQuality control — sound units, correct mortar grade, full and even joints, soaked bricks, proper curing, limited daily lift height, and supervision. The strength of a brittle material is a minimum assured value.
Three diagrams of a wall section comparing an un-reinforced wall breaking into two blocks, a core-reinforced wall and a wall with containment reinforcement showing distributed cracking
Fig. 3.18 Containment reinforcement as an earthquake-resistant feature: (a) un-reinforced — a single hinge and collapse; (b) core-reinforced; (c) containment reinforcement — the damage is distributed into many fine cracks and the wall holds together. Source: course lecture slides, IOE Pulchowk Campus.

3.8  Seismic Performance due to Various Factors

The syllabus lists nine factors explicitly. Each is a potential 2–4 mark sub-question.

(a) Geometrical and mass irregularities

Photograph of an L-shaped masonry building damaged at the re-entrant corner after an earthquake
Fig. 3.19 Damage concentrated at the re-entrant corner of an irregular (L-shaped) building. Source: course lecture slides.

(b) Opening size and location

Photograph of a masonry building with very large shopfront openings that has collapsed at ground floor level
Fig. 3.20a Large openings — the ground storey becomes a row of slender piers. Source: course lecture slides.
Photograph of cracking radiating from a window placed close to the corner of a masonry wall
Fig. 3.20b Openings at corners break the force path between the two walls. Source: course lecture slides.

(c) Eccentrically acting gravity load

(d) Eccentrically acting lateral force — torsion

(e) Rigid and flexible floor diaphragm

See §3.3.3 and Fig. 3.4. In summary:

AspectRigidFlexible
Shear distributionBy relative stiffnessBy tributary area
TorsionTransmittedNot transmitted
Support to out-of-plane wallsEffectivePoor — wall spans full height unaided
OverallEnables genuine box actionWalls behave individually → out-of-plane collapse

(f) Slender walls

Photograph of a long masonry wall without any cross walls that has bulged and required external propping
Fig. 3.21 A long wall with no cross walls bends horizontally out-of-plane and has to be propped. Source: course lecture slides.

(g) Horizontal and vertical bands

(h) Material properties

(i) Construction quality

(j) Pounding between adjacent buildings

Adjacent buildings of different height, mass or period vibrate out of phase and hammer each other. The damage is concentrated at floor level of the shorter building, where its slab strikes the taller building's column or wall mid-height. The remedy is an adequate seismic separation gap.

Photograph of two adjacent buildings of different heights damaged where they hammered against each other during an earthquake
Fig. 3.22 Pounding between adjacent blocks of different height and period. Source: course lecture slides.

3.9  Seismic Performance of Masonry Buildings during Past Earthquakes 2078 Bhadra2081 Bhadra

3.9.1  2015 Gorkha earthquake (Mw 7.8) 2078 Bhadra, Q1b

The major failure mechanisms observed in masonry buildings during the Gorkha earthquake were:

  1. Out-of-plane collapse of walls — by far the dominant mechanism, caused by unanchored flexible timber floors and roofs, the absence of bands and slender walls in the upper storeys.
  2. Corner separation and vertical cracking at wall junctions, from poor interlocking of the courses at the corners.
  3. Delamination and collapse of multi-wythe walls — both burnt-brick-in-cement and un-coursed random rubble walls with corrugated galvanised iron roofs, because of the missing through-stones.
  4. In-plane diagonal (X) shear cracking of piers between openings, and vertical cracking at the corners of openings.
  5. Failure of gable walls, which pulled down the top of the end walls and the roof.
  6. Separation of the roof from the walls, followed by collapse of heavy tiled roofs on the occupants.
  7. Failure of the soft/open ground storey in shop-front buildings and of the short columns created by mezzanines.
  8. Total collapse of unreinforced stone-in-mud houses in the rural districts around the epicentre, while buildings with even a single RC lintel band frequently survived with repairable damage — the clearest field evidence available for the value of banding.
  9. Widespread failure of temples, monuments and monasteries, several of which had already been weakened by earlier earthquakes, plus lifeline failures such as the collapse of a penstock in Sindhupalchowk.

3.9.2  2080 BS (2023) Jajarkot earthquake (M 6.4) 2081 Bhadra, Q2a

Although only a moderate M 6.4 event, it destroyed a very large number of houses because the building stock in Jajarkot and Rukum West is almost entirely random rubble stone masonry in mud mortar. The failure mechanisms specific to that construction are:

MechanismWhy it happened in stone-in-mud construction
Delamination of the wall through its thicknessThick two- or three-leaf walls with a loose rubble core and no through-stones; the leaves have no connection, so the outer leaf peels off and the wall loses most of its section.
Out-of-plane overturning of wallsFlexible timber/slate roofs simply resting on the walls, no anchorage, no bands, and heavy walls with a high h/t ratio.
Corner separation and disintegration at junctionsRounded and irregular stones give no interlocking at corners; mud mortar has essentially zero tensile and bond strength, so the corner simply comes apart.
Bulging and buckling of the wallRandom rubble with thick mud joints and no bond; the wall behaves as loose stacked stone once shaking begins.
Diagonal / stepped shear cracking of piersWeak mortar means the crack steps around the stones through the joints (§3.6.3, mode 3).
Collapse of the heavy mud-and-slate roofVery large mass high up, unanchored, so a large inertia force is applied to walls that cannot resist it; the roof then falls in.
Gable and parapet collapseNo gable band, no vertical load to stabilise them.
Loss of strength of the mud mortarRain before and after the event further weakened an already negligible bond.
Total (pancake) collapseOnce the walls disintegrated, the floors and roof lost all support — giving a very high fatality rate for a moderate earthquake.
The strengthening prescription for these buildings (asked as 2081 Bhadra Q2b): through-stones or substitutes at 1.2–1.5 m spacing in both directions; RC or timber bands at plinth, sill, lintel and eave level; vertical bars at corners and opening jambs; splint-and-bandage or wire-mesh-and-cement jacketing of the cracked walls; grouting of cracks; reduction and repositioning of openings; anchoring and lightening of the roof; and replacement of the mud mortar in the outer face by cement pointing.

3.9.3  Other reference earthquakes

EventLesson for masonry
1934 Nepal–Bihar, M 8.480,893 buildings destroyed and 126,355 damaged in the Valley; showed the vulnerability of tall, slender, unbanded brick towers (Dharahara) and of three-leaf walls.
1988 Udayapur, M 6.6Extensive damage to brick-in-mud buildings in eastern Nepal and Bhaktapur, at a magnitude usually considered moderate.
2001 Bhuj (Gujarat), Mw 7.7Collapse of stone and brick buildings in Bachau and Kutch; also demonstrated the value of RC lintel bands — a two-storey slate-and-block house with bands in both storeys survived undamaged next to collapsed neighbours.
2005 Kashmir, Mw 7.6Massive delamination of rubble stone masonry; renewed international interest in traditional timber-laced dhajji-dewari, which performed markedly better.
1985 Mexico City, M 8.1Resonance of mid-rise buildings with the soft lake-bed deposits — site effects can matter more than distance.
1989 Loma Prieta, USAFailure of unreinforced masonry buildings with large shopfront openings in the Marina District.
Model answer skeleton for “Failure mechanism of masonry buildings + mitigation measures, with sketches” [12 marks]
  1. Two lines on why masonry is vulnerable: brittle, heavy, weak in tension, and the walls carry everything.
  2. Classification — the seven-fold list of §3.6.1. (2 marks)
  3. In-plane modes with sketches — rocking, sliding, bed-joint stepped crack, diagonal tension X crack + toe crushing. Add the strong-mortar / weak-mortar diagnostic. (3 marks)
  4. Out-of-plane modes with sketches — simple overturning, composed overturning, vertical flexure, horizontal flexure. State that h/t and precompression govern. (3 marks)
  5. Other damage — corner separation, delamination, gable and roof failure, pounding. (1 mark)
  6. Mitigation table — the §3.7.6 list, each measure tied to the failure it prevents. (3 marks)

Quick Revision — Points to Memorise

  • Weak direction = perpendicular to the wall plane; strong direction = along the wall length. Horizontal shaking is the most damaging.
  • Shear wall = parallel to shaking (in-plane); cross wall = orthogonal (out-of-plane).
  • Magenes & Calvi's three mechanisms: shear cracking, sliding, rocking.
  • Four in-plane modes: rocking, sliding, bed-joint (stepped) diagonal shear, diagonal tension (X) + toe crushing.
  • Four out-of-plane mechanisms: simple overturning, composed overturning, vertical flexure, horizontal flexure. Governed by h/t ratio and vertical stress.
  • Stepped crack → weak mortar. Straight X crack through bricks → strong mortar + high compression.
  • Seven-fold damage classification (§3.6.1) — learn it as a list.
  • Rigid diaphragm → distribute by stiffness, transmits torsion. Flexible diaphragm → distribute by tributary area, no torsion.
  • Load combinations: DL+IL; DL+IL+(WL or EL); DL+(WL or EL); 0.9DL+(WL or EL). Permissible stress +1/3, or equivalently load ×0.75.
  • Torsion limits: CM–CR eccentricity < 30% of the plan dimension; minimum accidental eccentricity 5%.
  • Soft storey: stiffness ≥ 60% of the adjacent storey and ≥ 70% of the average of the three above. Weak storey: strength ≥ 70% of the adjacent storey. Mass irregularity: change ≤ 80%.
  • Openings: small, few, central, vertically aligned, ≥ 600 mm from the corner, total ≤ ~50% of the wall length.
  • Plan projections up to ~15–20% of the length need no seismic joint; beyond that, separate the blocks.
  • EMS damage grades G1–G5: G1/G2 repair, G3 grout + repair, G4/G5 vacate.
  • Jajarkot 2080 keyword: random rubble stone in mud mortar, no through-stones → delamination + out-of-plane collapse.

Chapter Summary

Masonry buildings are brittle and heavy, so ground shaking generates large inertia forces at the roof and floor levels that must travel through the walls to the foundation. A wall is strong when pushed along its length (in-plane, as a shear wall) and very weak when pushed perpendicular to its plane (out-of-plane, as a cross wall); because the shaking reverses and acts along both horizontal axes, every wall plays both roles, and it is the out-of-plane role that governs survival. Lateral load is collected by the floor and roof acting as horizontal diaphragms and delivered to the shear walls, which behave as vertical cantilevers designed for compression and shear with no tension. A rigid diaphragm distributes the storey shear in proportion to wall stiffness and can transmit torsion; a flexible diaphragm distributes by tributary area, cannot transmit torsion, and leaves the out-of-plane walls unsupported.

Survival depends on box action — the roof, walls and foundation acting as one closed box, achieved by corner interlocking, horizontal bands at plinth, sill, lintel, roof and gable level, vertical containment reinforcement, positive wall-to-roof anchorage and a stiff diaphragm. In-plane failure occurs by rocking, sliding, bed-joint (stepped) diagonal cracking or diagonal tension with toe crushing, the choice depending on the pier aspect ratio, the vertical precompression and whether the mortar is weaker or stronger than the units. Out-of-plane failure occurs by simple overturning, composed overturning, vertical flexure or horizontal flexure, governed by the height-to-thickness ratio and the vertical stress. Other characteristic damage includes corner separation, delamination of multi-leaf walls, failure of piers between openings, gable and parapet collapse, roof separation and pounding, all classified after the event on the five-grade EMS scale.

Performance is degraded by plan, vertical and mass irregularity, by large openings and openings near corners, by eccentric gravity load, by torsional eccentricity between the centre of mass and the centre of rigidity, by flexible diaphragms, by slender walls, by the absence of bands, by poor materials — above all mud mortar — and by poor workmanship. Field evidence from 1934, 1988, 2015 Gorkha and 2080 Jajarkot confirms all of it: unreinforced stone-in-mud houses delaminate and overturn, while otherwise identical buildings with simple RC bands and through-stones survive with repairable damage.

All Past Exam Questions from this Chapter

CHAPTER 3 — COMPLETE LIST (CE 72502 / ENCE 367)

  1. Discuss the failure mechanisms of the stone masonry buildings with mud mortar during the 2080 Jajarkot Earthquake. [8] (2081 Bhadra, Q2a) → §3.9.2
  2. Explain the strengthening procedure for the damaged masonry buildings. [8] (2081 Bhadra, Q2b) → §3.7.6 and Chapter 6
  3. Describe failure mechanism of masonry building during earthquake and suggest its mitigation measures to make earthquake resistant with sketches. [12] (2080 Bhadra, Q1b) → §3.6, §3.7.6
  4. Differentiate between in-plane and out-of-plane behaviour of masonry structures. Explain the different failure modes of masonry structures with a neat sketch. [8] (2079 Bhadra, Q2b) → §3.4, §3.6
  5. Describe in brief with sketch major failure mechanism of masonry building during Gorkha earthquake. [6] (2078 Bhadra, Q1b) → §3.9.1
  6. Discuss in brief failure mechanism of masonry structures and remedial measures. [10] (2076 Chaitra, Q3a) → §3.6, §3.7.6
  7. Explain different modes of failure in brick masonry structures with sketches for both static and earthquake load. [10] (2075 Chaitra, Q2) → §3.6.2 (static), §3.6.3–3.6.4 (seismic)

Note that 2081 Bhadra Q2b (“strengthening procedure for damaged masonry buildings”) sits on the boundary between this chapter and Chapter 6. Answer it with the mitigation table of §3.7.6 plus the repair/retrofit techniques of Chapter 6 — grouting and stitching of cracks, splint-and-bandage, wire-mesh jacketing, through-stones, addition of bands and vertical bars, and reduction of openings.