Chapter 2

Masonry Structures

8 Hours · 8 Marks 9 Past Questions · 58 Marks

Syllabus & Marks Distribution

DetailInformation
CourseSeismic Resistant Design of Masonry Structures — ENCE 367 (Elective I)
Chapter2 — Masonry Structures
Teaching Hours8 hours
Marks Allocation8 marks
Total Course Marks60 marks (final exam) · 45 teaching hours
Weight13.3% of the final paper
Key codesIS 1905–1987, IS 1077, NBC 101, NBC 109, NS 1:2035, SP 20

Syllabus Topics

  • 2.1  History of masonry structures in ancient and modern times
  • 2.2  Nature of masonry structures
  • 2.3  Mechanical and physical properties of masonry; masonry materials (units, mortar and walls)
  • 2.4  Types of masonry structures (load bearing, confined and infill masonry); types of walls
  • 2.5  Lateral force resisting elements (walls, piers and arches)
  • 2.6  Structural system of historical masonry structures; review on design of masonry walls for static force
  • 2.7  Emerging materials and technologies in masonry structures
Why this chapter matters more than its 8 marks suggest. Section 2.6 — the review of masonry wall design for static force — supplies the slenderness ratio, effective height/length/thickness, stress reduction factor, area reduction factor, shape modification factor and permissible compressive stress that every 12–18 mark wall/pier/column design numerical in the paper is built on. Learn this chapter properly and Chapters 4 and 5 become mostly arithmetic.

Importance & Frequently Asked Topics HIGH

Theory from this chapter has appeared in all 6 of the last 6 papers — a total of 58 theory marks, i.e. about 10 marks per paper. On top of that, the design factors defined in §2.6 are used in essentially every numerical in the paper. It is the single most reliable chapter to prepare.

Marks Distribution by Each Exam

ExamTheory marksQuestions asked
2075 Chaitra12Q3 — slenderness ratio & shape modification factor, and their influence on wall strength
2076 Chaitra16Q1a — factors affecting compressive strength of brick masonry; Q4b — stress reduction factor & confined masonry
2078 Bhadra12Q2a — masonry types by material with merits/demerits; Q2b — unit–mortar relation on strength
2079 Bhadra8Q2a — load-bearing, infill and confined masonry
2080 Bhadra8Q2a — properties & strength of brick masonry, affecting factors, unit–mortar relation
2081 Bhadra8Q3a — physical properties of bricks; Q4a — nature of masonry structure

Frequently Asked Topics

TopicTimes AskedFrequency
Factors affecting strength of masonry & the unit–mortar relationship3
Types of masonry — load bearing, confined, infill (and by material)3
Properties of bricks / of brick masonry2
Slenderness ratio, stress reduction factor, shape modification factor2
Nature of masonry structures1
Types of walls; lateral force resisting elementsindirect
History & emerging materials0 direct

Topic-wise Importance & Exam Tips

TopicImportanceKey Points / Exam Tips
Factors affecting compressive strength of masonryHighGroup into unit – mortar – geometry – workmanship. Always state the key rule: masonry strength is only 25–50% of unit strength, and mortar must be weaker than the unit. Draw the prism failure sketch.
Relation between unit and mortar strengthHighExplain the lateral-tension mechanism: mortar is softer, tries to spread sideways, and puts the unit into lateral tension. Then quote the optimum-mortar rule from IS 1905/SP 20.
Load bearing vs confined vs infill masonryHighAnswer with a load-path sentence + sketch for each, then a comparison table. Confined masonry: walls built first, tie-columns cast against them — that is what distinguishes it from an RC frame with infill.
Physical & mechanical properties of bricksHighSplit clearly: physical (size, shape, colour, texture, density, water absorption, efflorescence, soundness, hardness) vs mechanical (compressive strength, modulus, tensile/flexural). Quote NS 1:2035 size 240×115×57 mm and water absorption ≤ 15%.
Slenderness ratio & its effect on strengthHighSR = effective height/effective thickness (or effective length/effective thickness — take the lesser). Show the failure-stress vs SR curve: crushing at low SR, buckling at high SR. Quote the limiting values table.
Stress reduction factor ksHighTable 9 of IS 1905, function of SR and e/t. State that it is 1.0 for SR ≤ 6 and e = 0.
Shape modification factor kpMediumTable 10, function of height/width ratio of the unit as laid; applies only to units of crushing strength up to 15 N/mm². Taller units → fewer bed joints → higher strength.
Nature of masonry structuresMediumSix words to build the answer around: composite, heterogeneous, anisotropic, brittle, heavy, workmanship-sensitive.
Types of walls; piers, spandrels, arches, bandsMediumLearn the URM element diagram (pier / spandrel / in-plane wall / out-of-plane wall / diaphragm / parapet) — it also answers Chapter 3 and 4 questions.
Mortar types and gradesMediumMemorise the H1/H2/M1/M2/M3/L1/L2 idea and 3–4 mix proportions. Note cement mortar richer than 1:3 is never used and leaner than 1:5–1:6 becomes harsh.
History; emerging materials & technologiesLowNot yet asked directly, but both are explicitly in the new syllabus. Keep a 6-point timeline and a 6-item list of modern materials ready.

2.1  History of Masonry Structures in Ancient and Modern Times

Masonry is the oldest structural material still in everyday use. It has been employed for at least 10,000 years in houses, private and public buildings and historical monuments. The masonry of ancient times involved two major materials: brick manufactured from sun-dried mud or burned clay and shale, and natural stone.

2.1.1  Ancient masonry

2.1.2  Masonry in Nepal

2.1.3  Modern masonry

PeriodDevelopment
Mid-1800sFired clay brick becomes the principal building material of industrialised countries.
1891The 16-storey Monadnock Building, Chicago — the tallest load-bearing masonry building ever built, with 1.8 m thick walls at the base. It shows the limit of empirical design.
Early 1900sConcrete masonry is introduced and, along with clay masonry, expands into all types of structure.
After WW I / WW IIReinforced brickwork is used in India and Japan from after the First World War, and in America from after the Second.
Last ~50 yearsIntroduction of engineered (calculated) masonry and reinforced masonry, producing structures that are much stronger and more stable against wind and seismic loads. Codes such as IS 1905, NBC 109 and Eurocode 6 replace the rules of thumb.
Recent decadesConfined masonry emerges worldwide as an economical middle path between unreinforced masonry and RC frames; prestressed masonry, thin-joint systems and industrial blocks appear.

2.2  Nature of Masonry Structures 2081 Bhadra, Q4a

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. Describe the nature of the masonry structure. [4] (2081 Bhadra, Q4a)
  2. Define masonry structure type based on materials with its advantages and disadvantages. [6] (2078 Bhadra, Q2a)

2.2.1  What is masonry?

Masonry is a composite structural material formed by bonding together individual masonry units (clay brick, dried earth, stone, concrete block, etc.) with layers of mortar (cement, lime, cement–lime or mud), together with metal ties, reinforcement and accessories where required, to form walls, columns, arches, domes and other structural elements.

Unreinforced masonry (URM) is construction made of masonry units set in mortar without any reinforcement. It has no tension-resisting elements and relies on gravity load for its lateral resistance. It is this building type — not engineered masonry — that is responsible for the great majority of earthquake deaths worldwide.

2.2.2  Nature (essential character) of masonry — the exam answer

CharacteristicExplanation and structural consequence
Composite / two-phaseIt is not one material but two — stiff, strong units bedded in a softer, weaker mortar. Behaviour is governed by the interaction between them and by the unit–mortar bond, not by either alone.
Heterogeneous & highly variableProperties scatter significantly from point to point in the same wall. Design values are therefore conservative “minimum assured” values.
Anisotropic (directional)Because the bed joints and head joints form continuous planes of weakness, strength and stiffness depend on the direction of loading relative to the joints. A masonry wall is far stronger loaded perpendicular to the bed joints than parallel to them.
Strong in compression, very weak in tension and shearCompressive strength is high, so masonry suits walls, columns, arches and domes. Tensile strength is almost negligible, so masonry cannot be used for beams or slabs, and cracks as soon as flexural tension appears.
Brittle, with little ductilityIt fails suddenly with little warning and dissipates very little energy — the opposite of what is wanted under cyclic earthquake loading.
Heavy — large massSelf weight is large, so the inertia force F = m a attracted in an earthquake is large, and heavy foundations are needed. Mass is both its stabiliser (gravity friction) and its enemy (seismic demand).
ModularThe unit fixes the module; wall thicknesses, lengths and opening sizes are all multiples of the unit dimension plus a joint.
Extremely sensitive to workmanshipFull and even bed joints, proper vertical joint filling, correct bond and corner interlocking, and curing govern the actual strength far more than the nominal design.
Non-engineered by traditionMost masonry worldwide is still built by artisans without any structural calculation — the definition of “non-engineered construction”.

2.2.3  Where masonry is used

Masonry is normally used for components subjected to compressive loading: (1) walls, (2) columns, (3) arches, (4) domes. Masonry walls also have a limited capacity to carry horizontal loads and bending moments. Masonry is used not only for pure masonry buildings but also, very successfully, in mixed structures — for example masonry infill in RC or steel frames.

2.2.4  Advantages and Disadvantages of Masonry 2078 Bhadra, Q2a

Advantages

  1. High compressive strength — ideal for walls, columns and arches, which are in pure compression.
  2. Durable — usually no finish is required.
  3. Made from raw materials that are locally available at low cost.
  4. No complicated plant or skilled machinery is required; labour-intensive, so it suits developing economies.
  5. Attractive appearance and design flexibility — units can be combined to form complex shapes.
  6. Good fire resistance and good thermal and acoustic properties; increases the thermal mass of the building.
  7. Brick usually needs no painting, giving low life-cycle cost.
  8. Masonry built in compression with lime mortar can last more than 500 years, against 30–100 years for steel or RC.

Disadvantages

  1. Very low tensile strength — cannot be used for flexural elements such as beams or slabs.
  2. Heavy compared with timber — larger foundations are needed and transport costs are higher; it also attracts large seismic inertia forces.
  3. Brittle — poor ductility and energy dissipation, so it performs badly in earthquakes.
  4. Frost and chemical (sulphate) attack cause spalling of brickwork.
  5. Efflorescence — chalky, unsightly (but harmless) salt deposits after cycles of wetting and drying.
  6. Extreme weather degrades wall surfaces.
  7. Demands a strong foundation (e.g. RC) to avoid settlement and cracking.
  8. Not well suited to tropical climates with heavy heat and rain; construction is slow and weather-dependent.

2.3  Mechanical and Physical Properties of Masonry; Masonry Materials 2076 Chaitra2078 Bhadra2080 Bhadra2081 Bhadra

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. What are the physical properties of bricks? [4] (2081 Bhadra, Q3a)
  2. Define properties and strength of brick masonry, affecting factors and relation of unit and mortar on strength of masonry. [8] (2080 Bhadra, Q2a)
  3. Describe affecting factors and relation between unit and mortar on strength of brick masonry. [6] (2078 Bhadra, Q2b)
  4. State and explain briefly the factors affecting the compressive strength of brick masonry. [8] (2076 Chaitra, Q1a)
Slide listing masonry units (clay brick, calcium silicate brick, concrete block, stone, compressed earth) and mortars, with sketches of a stock brick, Fletton brick and the frog, stretcher and perpend of a brick
Fig. 2.1 The two constituents of masonry — the units and the mortar — together with the standard terminology of a brick (frog, stretcher face, perpend). Source: course lecture slides, IOE Pulchowk Campus.

2.3.1  Masonry Units

A masonry unit is a brick, tile, stone, glass block or concrete block conforming to the requirements of the relevant code. The main families are:

UnitDescriptionTypical use / remark
Burnt clay brickMoulded clay fired in a kilnThe standard structural unit in Nepal; strength 3.5–35 N/mm²
Sun-dried earth / adobeMud blocks dried in the sunCheapest; very weak, water-sensitive, extremely vulnerable in earthquakes (NBC 204)
StoneRandom rubble, coursed rubble, squared/dressed stone, ashlarDominant in hill and mountain Nepal; strong units but very weak wall because of poor bond (NBC 203)
Concrete block (CMU)Cement + aggregate blocks larger than 305×102×102 mmFast, dimensionally accurate; hollow or solid
Calcium silicate / sand-lime brickLime + sand, autoclavedAccurate size, uniform colour
Compressed earth block (CEB)Soil, sometimes stabilised with 5–8% cement, compressed in a pressLow energy, low cost, growing use in Nepal
Hollow / perforated units, partition tilesUnits with voidsLighter, better insulation; voids improve mortar keying
Hollow unit — net cross-sectional area in any plane parallel to the bearing surface is less than 75% of the gross area in that plane.
Solid unit — net area in every such plane is 75% or more of the gross area.
Illustration of masonry unit types: brick wall with mortar, firebrick, perforated brick, hollow brick, partition tile and solid brick
Fig. 2.2 Common types of masonry unit. Source: course lecture slides, IOE Pulchowk Campus.

Physical properties of bricks 2081 Bhadra, Q3a

PropertyRequirement / typical value
Size (Nepal Standard NS 1:2035)240 × 115 × 57 mm with a 10 mm mortar joint. Note the modular rule: length of brick = 2 × width + 1 vertical mortar joint. (Modular brick in IS 1077 is 190×90×90 mm, nominal 200×100×100 mm; the common Nepali site brick is often quoted as 230×110×55 mm.)
ShapeRegular, truly rectangular with sharp, square edges and parallel faces; free from warpage, distortion and bowing.
Colour and textureDeep cherry red or copper colour, uniform throughout; even, fine-grained, compact texture free from grit or lumps.
SoundnessShould emit a clear ringing (metallic) sound when two bricks are struck together, and should not break when dropped flat from about 1 m.
HardnessNo impression should be left when scratched with a finger nail.
Water absorptionNot more than 15% of its weight after 24 hours immersion in water at normal temperature. Hand-made bricks with keys (frogs) may absorb up to 25%.
EfflorescenceShould be nil to slight — no white salt deposit after immersion and drying.
Density / unit weightAbout 1800–2000 kg/m³ for brick; brick masonry is usually taken as 19–20 kN/m³.
Structural qualityThoroughly burnt, free from cracks, flaws, nodules of lime and organic matter.

Mechanical properties

PropertyTypical value / relationship
Compressive strength of the unit3.5–40 N/mm² (IS 1905 Table 8 covers 3.5 to 40). Ordinary Nepali kiln brick is 5–12 N/mm².
Compressive strength of the masonryOnly about 25–50% of the unit strength — the joints, not the bricks, govern.
Tensile / flexural (bond) strengthVery low, typically 0.1–0.4 N/mm² and effectively zero for mud mortar. IS 1905 allows a permissible flexural tensile stress of only 0.07–0.14 N/mm².
Shear strengthGoverned by cohesion + friction. IS 1905: permissible shear stress fs = 0.1 + fd/6, subject to a maximum of 0.5 N/mm², where fd is the compressive stress due to dead load.
Modulus of elasticity EmCommonly taken as Em ≈ 550 to 1100 fm (often 750 fm); i.e. a few thousand N/mm². Much lower than concrete.
Poisson's ratioAbout 0.15–0.20
Modulus of rigidity GAbout 0.4 Em

2.3.2  Mortar

Mortar is a plastic mixture of approved cementitious material, fine aggregate and water that bonds masonry units together, compensates for dimensional variations in the units, seals the joints against rain and distributes the load uniformly over the bed.

Requirements of a good mortar

Types of mortar

TypeProportionsCharacteristics
Cement mortarCement : sand, 1:3 to 1:8Sets early and gains strength quickly; can set and harden in wet locations. Richer than 1:3 is never used in masonry — it causes high shrinkage and does not increase masonry strength. Leaner than about 1:5–1:6 becomes harsh, unworkable and prone to segregation, and lean mortars do not fill the voids in the sand so they are not impervious.
Lime mortarLime : sand (or surkhi/cinder), 1:2 to 1:3Gains strength slowly and has low ultimate strength; fat-lime mortar does not harden at all in wet locations. Its great merits are good workability, good water retentivity and low shrinkage, so lime masonry resists rain penetration well and is less liable to crack. Hydraulic lime is better than fat lime; with fat lime a pozzolana (surkhi, cinder, fly ash) must be added.
Cement–lime mortarCement : lime : sand, 1:1:6, 1:2:9, 1:3:12Combines the good qualities of both — medium strength with good workability, good water retentivity, freedom from cracks and good rain resistance. Keeping binder : sand = 1:3 gives a very dense mortar because the sand voids are fully filled.
Mud mortarClayey soil + waterAttains some strength on drying but readily absorbs moisture and loses its strength when wet, and has poor bonding quality. Used only for temporary and low-cost single-storey rural houses. It is the main reason stone-in-mud houses collapse in Nepali earthquakes.

Mortar grades (NBC 101 / IS 1905)

Mortars are classified for design convenience as H (high strength), M (medium) and L (low). The mortar type must be matched to the strength of the masonry unit:

S.No.CementLimeSandMin. 28-day compressive strength (N/mm²)Mortar typeSuitable unit strength (N/mm²)
110 to 0.25 C310.0H125 or above
2(a)1047.5H215 to 24.9
2(b)10.5 C4.56.0H2
3(a)1055.0M15 to 14.9
3(b)11 C63.0M1
4(a)1063.0M2Below 5
4(b)12 C92.0M2
4(c)01 A2 to 32.0M2
5(a)1080.7L1—
5(b)13 C120.7L1

Notes. A, B and C denote eminently hydraulic, semi-hydraulic and fat lime respectively. Mortar strength varies appreciably with the angularity, grading and fineness of the sand, so the sand content may be reduced where necessary. With plain cement–sand mortars a plasticiser should be added to improve workability. 1 N/mm² = 1 MPa = 10.2 kg/cm². For first-class brickwork the mortar should be H1 or H2.

Table of recommended mortar mixes by construction category, giving cement-sand and cement-lime-sand proportions from 1:4 to 1:7
Fig. 2.3 Recommended mortar mixes by category of construction. Note how the richer mix is demanded for the more critical category.Source: course lecture slides, IOE Pulchowk Campus.

2.3.3  Bonds and Brick-laying Terminology

A bond is the pattern in which units are laid. In a single-thickness wall the bond is largely decorative, but in double-thickness walls the bond is structural — it ties the leaves together and prevents continuous vertical joints, which would otherwise split the wall.

TermHow the brick is laid
StretcherHorizontally, flat, with the long side exposed on the wall face
HeaderHorizontally, flat, with the short end exposed
SoldierVertically, with the narrow (stretcher) side exposed
SailorVertically, with the broad side exposed
Rowlock (bull header)On the long narrow side, with the header face exposed
ShinerOn the long narrow side, with the broad face exposed
Queen closerA brick cut lengthwise to half width, used next to the quoin header to create the face lap
PerpendThe vertical (head) joint between two units in the same course
FrogThe indentation in the bed face of a brick that keys the mortar
Diagram naming the brick laying positions: stretcher, header, soldier, sailor, shiner and rowlock
Fig. 2.4 Brick-laying positions.Source: course lecture slides.
Isometric drawing of a brick wall corner with header, stretcher and closer bricks labelled
Fig. 2.5 Header, stretcher and closer in a wall.Source: course lecture slides.
BondDescriptionRemark
English bondAlternate courses of all headers and all stretchers on both faces. Each header course starts with a quoin header followed by a queen closer; stretchers lap a minimum of a quarter brick over the headers.Strongest bond — no continuous vertical joints. Adopted for most load-bearing masonry that is to be plastered. Header joints must be kept thin or the face lap disappears.
Flemish (Dutch) bondAlternate headers and stretchers within each course; the header of one course sits centrally over the stretcher of the course below.Most decorative; needs the perpends to line up vertically, which is hard to achieve. Slightly weaker than English bond, but wastes fewer good-quality face bricks.
Rat-trap bondBricks laid on edge so that shiners and rowlocks show on the face, creating an internal cavity bridged by the rowlocks.Uses about 25–35% fewer bricks and gives good thermal insulation. Popularised in India by Laurie Baker. It is a modular technique — wall and opening dimensions are set by the brick size.
Stretcher (running) bondAll stretchers, each lapping half a brickOnly for half-brick partitions and veneers — not load bearing.
Header bondAll headersUsed for curved walls and footings.
Isometric drawings of two brick bond corners showing alternating Course A and Course B
Fig. 2.6 Alternating courses A and B at a corner — this is what breaks the vertical joints and gives the bond its strength.Source: course lecture slides.
Photographs and isometric drawing of a rat-trap bond wall corner with bricks laid on edge forming internal cavities
Fig. 2.7 Rat-trap bond — bricks on edge with an internal cavity. Source: course lecture slides.

2.3.4  Strength of Masonry — Unit–Mortar Interaction 2078 Bhadra, Q2b2080 Bhadra, Q2a

The compressive strength of masonry is not the strength of the brick, and it is not the strength of the mortar. It is governed by the interaction between them:

The mechanism. Under vertical compression the mortar is softer and has a higher Poisson's ratio than the unit, so it tries to expand sideways more than the unit does. Friction and bond at the interface prevent it from doing so freely. The result is that the mortar is put into triaxial compression (which strengthens it) while the unit is put into lateral tension combined with vertical compression.

Because masonry units are weak in tension, failure starts as vertical splitting cracks through the units, not by crushing of the mortar. This is why:
  • masonry strength is only about 25–50% of the unit strength;
  • increasing the mortar strength gives a less than proportionate gain in masonry strength — doubling mortar strength may raise masonry strength by only 15–25%;
  • a thinner bed joint gives a stronger wall, because less soft material means less lateral tension;
  • the mortar should be weaker than the unit — a mortar stronger than necessary is wasteful, cracks the units rather than the joints, and produces brittle, unrepairable failure.
Unit (stiff, strong) Mortar (soft, weak) Vertical compression Lateral TENSION in the unit Mortar restrained → triaxial compression Vertical splitting cracks through the UNITS — the characteristic compression failure of a masonry prism —
Fig. 2.8 Why masonry is weaker than its bricks. The soft mortar tries to bulge sideways, is restrained by the unit, and in reaction puts the unit into lateral tension — so the prism splits vertically.

Empirical relations

A widely used form (Eurocode 6 / IS SP 20 type expression) is

fk  =  K · fbα · fmβ    with typically α ≈ 0.7 and β ≈ 0.3

fk = characteristic compressive strength of masonry, fb = strength of the unit, fm = strength of the mortar, K = constant for the unit/bond type.

The exponents say it all: unit strength matters more than twice as much as mortar strength.

2.3.5  Factors Affecting the Compressive Strength of Brick Masonry 2076 Chaitra, Q1a2078 Bhadra2080 Bhadra

This is the most frequently asked theory question of the chapter. Organise the answer in four groups:

GroupFactorEffect on masonry strength
A. The unitStrength of the masonry unitThe single most important factor. Masonry strength rises with unit strength, but only to about 25–50% of it.
Shape, size and height/width ratio of the unit (as laid)A taller unit means fewer bed joints per metre of wall, so less soft material and less lateral tension → higher strength. Accounted for by the shape modification factor kp.
Frogs, perforations and voidsReduce the net bearing area and can cause stress concentration; hollow units are weaker per gross area.
Water absorption / suction rateA very absorbent dry brick sucks the water out of the mortar before it can hydrate, destroying the bond. Bricks must be soaked before laying.
B. The mortarStrength and grade of mortarIncreases masonry strength, but far less than proportionately. Mortar should be as weak as is permissible — not stronger than the unit.
Mix proportion and workabilityRich mixes (>1:3) shrink and crack; lean mixes (<1:6) are harsh, segregate and leave voids. Good workability → full joints → higher strength.
Water retentivity, deformabilityA mortar that is too stiff or too deformable both reduce strength; a more deformable mortar increases the lateral tension in the unit.
C. Geometry of the masonryThickness of the mortar jointVery significant. Strength decreases as joint thickness increases — a 10 mm joint is standard; a 20 mm joint can lose 20–30% of the strength.
Slenderness ratioHigher SR → buckling governs instead of crushing → permissible stress reduced by ks.
Eccentricity of loadingEccentric load adds bending, so the compressive stress on one face is much higher; permissible stress reduced by ks.
Cross-sectional areaSmall sections have less redundancy and greater relative effect of a single defect — hence the area reduction factor ka for areas below 0.2 m².
D. Workmanship & constructionBond pattern and corner interlockingContinuous vertical joints (poor bond) split the wall into independent leaves and drastically reduce strength.
Filling of vertical (head) jointsUnfilled perpends are one of the commonest defects; they reduce shear and compressive strength.
Uniformity and fullness of bed joints; verticality (plumb)Uneven joints create local stress concentrations; out-of-plumb walls introduce unintended eccentricity.
Curing and ageCement mortar needs curing; masonry strength continues to develop for 28 days and beyond.
Rate of construction / height of lift per dayBuilding too fast overloads green mortar and squeezes the joints.
Model answer skeleton for “Factors affecting the compressive strength of brick masonry” [8 marks]
  1. One line: masonry strength ≈ 25–50% of unit strength — it is the joints that govern.
  2. The unit–mortar interaction mechanism with Fig. 2.8 (2–3 marks are here).
  3. The four-group table above — give at least 8–10 factors with a one-line effect each.
  4. Close with the design consequence: this is why IS 1905 multiplies the basic compressive stress by ks, ka and kp (§2.6).

2.4  Types of Masonry Structures and Types of Walls 2076 Chaitra2078 Bhadra2079 Bhadra

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. Explain load-bearing masonry walls, infill masonry, and confined masonry. [8] (2079 Bhadra, Q2a)
  2. Define masonry structure type based on materials with its advantages and disadvantages. [6] (2078 Bhadra, Q2a)
  3. Explain the following applied to masonry structures: (ii) Confined masonry. [4] (2076 Chaitra, Q4b)

2.4.1  Classification by Material 2078 Bhadra, Q2a

TypeAdvantagesDisadvantages
Brick masonry
(burnt clay units)
Uniform shape and size → good bond and thin joints; good strength (3.5–35 N/mm²); easy to lay openings and bands; durable, fire and weather resistant; locally manufactured. Needs good clay, fuel and kilns (energy and pollution); quality varies between kilns; heavy; weak in tension.
Stone masonry
(random rubble, coursed rubble, squared, ashlar)
Very high unit strength; extremely durable; locally available free of cost in hill areas; attractive; good thermal mass. Irregular shapes give poor bond and very thick joints; walls are usually multi-leaf and delaminate; very heavy; needs skilled masons; the worst-performing type in Nepali earthquakes, especially random rubble in mud mortar.
Concrete block masonry Accurate dimensions, fast construction (large units), fewer joints, uniform quality, can be reinforced through the hollow cores. Needs cement and a plant; drying shrinkage cracking; heavier per unit if solid; higher initial cost.
Adobe / earthen masonry Cheapest; zero-energy production; excellent thermal comfort; entirely local material and skills. Very low strength, no tensile capacity, degrades on wetting, erodes; extremely vulnerable in earthquakes (see NBC 204).
Composite / faced masonry Combines an economical backing (rubble, block) with a good-quality facing (brick, ashlar). The two leaves have different stiffness and may separate if not properly bonded through with headers.

2.4.2  Classification by Structural System 2079 Bhadra, Q2a

This is the key classification for the exam. The distinguishing feature is the load path and whether the wall is a structural element or not.

(A) Load-bearing masonry

(B) Confined masonry 2076 Chaitra, Q4b(ii)

Confined masonry consists of load-bearing masonry wall panels that are confined on all four sides by lightly reinforced concrete tie-columns (vertical ties) and tie-beams (horizontal ties).

The defining construction sequence: the masonry wall is built FIRST, with toothed vertical edges, and the tie-columns are then cast against the completed wall. In an RC frame with infill it is the exact opposite — the frame is cast first and the wall is built into it afterwards. This is the single sentence that separates the two systems in an exam answer.

Structural components of a confined masonry building: masonry walls (carry gravity load down and act as bracing panels against horizontal force); confining elements (restrain the walls, prevent complete disintegration and ensure vertical stability); floor and roof slabs (transmit gravity and lateral load to the walls, acting as horizontal diaphragms); plinth band (transmits wall loads to the foundation and protects ground-floor walls from differential settlement in soft soil); and the foundation.

Isometric drawing of a two-storey confined masonry building labelled with slab, confining beams and columns, walls, plinth and foundation
Fig. 2.9 A confined masonry building — walls confined by RC tie-beams and tie-columns, on a plinth band and foundation.Source: course lecture slides.
Labelled isometric of a typical single storey confined masonry building identifying confining RC tie elements, door frame, confined masonry panel, wall anchors, foundation, tie beam and window frame
Fig. 2.10 Typical single-storey confined masonry building — 1 confining RC tie elements, 2 door frame, 3 confined masonry panel, 4 wall anchors, 5 foundation, 6 tie beam, 7 window frame. Source: course lecture slides.
Photograph of a single storey confined brick masonry house in Aceh, Indonesia, showing the RC tie-columns at the wall ends
Fig. 2.11 A single-storey confined brick masonry house (Aceh, Indonesia). The tie-columns are visible at the wall ends and at every opening.Source: course lecture slides.

(C) Infill masonry

(D) Unreinforced vs reinforced masonry

BasisUnreinforced masonry (URM)Reinforced masonry
Design assumptionFlexural tensile stresses are resisted by the masonry; any reinforcement present is neglected in designFlexural tensile stresses cannot be resisted by the masonry and are resisted by reinforcement only
ShearResisted by masonry aloneResisted by masonry or reinforcement, singly or in combination
MethodLinear elastic range; working stress designAllowable stress design or strength design
Seismic performanceBrittle; vulnerable to collapse; elements may “peel” off the building onto occupants and passers-byDuctile; much better under cyclic load
Note“Unreinforced masonry” can in fact contain reinforcement placed for structural integrity or by prescription — the term refers to the design assumption, not to the absence of steel.

Reinforced brickwork has been used in India and Japan since after the First World War and in America since after the Second. Bars are placed in the voids created by particular bonds and/or in the bed joints; bed-joint reinforcement in particular enhances the capacity of walls to resist lateral loading. Post-tensioning is also used for retaining walls, tanks and footbridges. Reinforced masonry is the subject of Chapter 5.

Cutaway illustration showing load transfer in a framed structure from distributed and concentrated loads on the slab, into beams, then columns, then spread footings and the ground
Fig. 2.12 Load path in a framed structure — slab → beam → column → footing → ground. In a load-bearing masonry building the beams and columns are replaced by the walls themselves. Source: course lecture slides.

Comparison of the three systems

BasisLoad-bearing masonryConfined masonryInfill masonry (RC frame)
Primary vertical load pathWallsWalls (ties assist)Beams and columns
Primary lateral resisting elementWalls acting in-planeConfined wall panelsFrame + infill acting as a diagonal strut
Construction sequenceWalls onlyWall first, then tie-columns cast against itFrame first, wall built into it afterwards
Is the wall a structural element?YesYesNominally no (but behaves as one)
Ductility / seismic performancePoor unless banded and reinforcedGood — ties contain the damageDepends on the frame; risk of soft storey and short column
Economy & skillCheapest, least skillModerate cost, moderate skillMost expensive, needs engineering
Suitable height1–3 storeysUp to about 3–4 storeysMulti-storey

2.4.3  Types of Walls

ClassificationTypeDescription
By functionLoad-bearing wallCarries vertical load from the roof/floor in addition to its own weight.
Non-load-bearing wallCarries only its own weight — partition, panel, curtain, parapet, free-standing and compound walls.
By constructionSolid wallSingle leaf of full thickness, e.g. half-brick (115 mm), one-brick (230 mm), one-and-a-half brick (350 mm).
Cavity wallTwo leaves separated by a continuous air cavity (50–100 mm) and tied by metal ties. Gives thermal insulation and prevents rain penetration. Its effective thickness for design is two-thirds of the sum of the two leaf thicknesses, or the thickness of the thicker leaf, whichever is greater.
Collar-jointed wallTwo leaves separated by a narrow vertical joint fully filled with mortar or grout.
Faced wallFacing and backing of different materials bonded together so that they act as one unit under load.
Veneered wallA facing attached to the backing but not bonded to it — the facing carries no load.
By structural roleShear wallA wall designed to resist lateral force acting in its own plane. The principal earthquake-resisting element of a masonry building.
Cross wallA wall perpendicular to another that stiffens it and reduces its effective length.
Panel wallAn exterior non-load-bearing wall in a framed structure, wholly supported at each storey.
Curtain wallA non-load-bearing wall spanning between columns/piers, subject only to its own weight and wind/seismic load on itself.
Free-standing wallNot laterally supported — compound and parapet walls. Limiting slenderness ratio only 10.
Retaining wallResists lateral earth pressure.

2.5  Lateral Force Resisting Elements (Walls, Piers and Arches)

2.5.1  The Three Primary Elements of a URM Building

Any masonry building resisting an earthquake can be reduced to three primary elements. Which role a wall plays depends entirely on the direction of shaking at that instant — and because shaking reverses and acts in both horizontal directions, every wall plays both roles in turn.

ElementRole
In-plane wall (shear wall)Parallel to the shaking. Stiff and strong in this direction; carries the storey shear by in-plane shear and flexure. Fails by diagonal (X) cracking, sliding, toe crushing or rocking.
Out-of-plane wallPerpendicular to the shaking. Behaves as a vertical slab spanning between the floor and the roof (and horizontally between cross walls). Very weak — overturns and collapses. This is the dominant collapse mechanism of URM.
Diaphragm (floor / roof)Horizontal plate that collects the inertia force from the out-of-plane walls and distributes it to the in-plane walls. A rigid diaphragm (RC slab) distributes force in proportion to wall stiffness; a flexible diaphragm (timber joists, CGI sheet) distributes in proportion to tributary area and leaves the out-of-plane walls unsupported.
Isometric drawing of a single storey brick building labelling the in-plane wall, out-of-plane wall, diaphragm, parapet, spandrel and pier, with the direction of earthquake motion indicated
Fig. 2.13 The three primary elements of an unreinforced masonry building — in-plane wall, out-of-plane wall and diaphragm — together with the parapet, spandrel and pier. Source: course lecture slides, IOE Pulchowk Campus.

2.5.2  Piers and Spandrels

2.5.3  Arches

2.5.4  Bands, Ties and Box Action

Individually strong walls are not enough — they must be tied together so the building behaves as a single closed box. The elements that provide this box integrity are:

ElementPurpose
Plinth bandTransmits the wall load to the foundation and ties the walls at plinth level. Required wherever the soil is soft or uneven in its properties.
Sill bandAt window sill level; limits the vertical cracking that starts at the corners of openings.
Lintel bandThe most important band. It must be provided in all storeys and all walls, and shall incorporate all door and window lintels (the lintel reinforcement being extra to the band steel). It gives the walls horizontal bending strength for out-of-plane inertia and ties orthogonal walls together.
Roof / eave bandProvided at eave level of trussed roofs and at floors made of joists and covering elements, to integrate them at their ends and fix them into the walls.
Gable bandEncloses the triangular gable masonry; its horizontal part is continuous with the eave-level band on the longitudinal walls. Alternatively use a truss or open gable clad in light sheeting.
Vertical (containment) reinforcementBars at corners, wall junctions and the jambs of openings, anchored into the bands, that resist the tension caused by overturning and rocking.
Wall anchors / roof-to-wall connectionPrevents the roof from sliding off and lets the diaphragm actually deliver its force to the walls.
Toothed or stepped vertical joint at wall junctionsFull bond between perpendicular walls, achieved by building the corners first to a height of 600 mm and then filling in between, or by a toothed joint made in each wall alternately in lifts of about 450 mm.

Note. If the wall height up to eave level is 2.5 m or less, the lintel-level band may be omitted and the lintel integrated with the eave-level band.

Isometric drawing of a masonry building showing the RC roof band, RC lintel band, RC sill band and vertical containment reinforcement in the masonry wall
Fig. 2.14 Masonry building with horizontal bands and vertical containment reinforcement. Source: course lecture slides.
Detail drawing of alternating toothed joints at the corner and T-junction of masonry walls, with 450 mm lifts
Fig. 2.15 Typical detail of toothed jointing at corners and T-junctions in 450 mm lifts (NBC 109, 1994).Source: course lecture slides.

2.6  Structural System of Historical Masonry Structures; Review on Design of Masonry Walls for Static Force 2075 Chaitra2076 Chaitra2080 Bhadra

PAST EXAM QUESTIONS ON THIS TOPIC:

  1. Explain the following and state the influence of it on strength of the wall: (i) Slenderness ratio (ii) Shape modification factor. [12] (2075 Chaitra, Q3)
  2. Explain the following applied to masonry structures: (i) Stress reduction factor. [4] (2076 Chaitra, Q4b)
  3. Explain the design criteria of walls subjected to transverse loading. [8] (2076 Chaitra, Q2a)
  4. Calculate the effective height, effective length, effective thickness and slenderness ratio of walls A, C, G and P. [12] (2080 Bhadra, Q2b)
  5. Plus every wall / pier / column design numerical: 2075 Q4, 2078 Q3–Q6, 2079 Q3b & Q4b, 2080 Q3a–b, 2081 Q3b.

2.6.1  Structural System of Historical Masonry Structures

FeatureDescription and structural consequence
Thick multi-leaf (three-wythe) wallsGood facing brick on both faces with a weak rubble-and-mud core. The three leaves are rarely tied by through-headers, so they delaminate and buckle outwards under shaking.
Mud or weak lime mortarAlmost no bond or tensile strength; loses strength completely when wet.
Massive walls, tapering with heightStability by gravity and by the middle-third rule rather than by any tensile capacity.
Flexible timber floors and roofsTimber joists simply rest on the walls without anchorage — there is no diaphragm action, so the out-of-plane walls are unsupported at the top and the walls act independently instead of as a box.
Heavy roofsHeavy tiles or thick mud overlay high up in the building → large inertia force at the worst possible level.
Large and irregular openingsElaborately carved windows and wide shop-front openings at ground level produce slender piers and a soft ground storey.
Arches, corbels, domes and vaultsCompression-only elements that develop horizontal thrust; they spread and hinge under lateral shaking.
Absence of bands and vertical tiesNo horizontal reinforcement at all — the corners separate first.
Beneficial traditional featuresTimber pegs and through-timbers acting as crude ties, timber bands in some Newari and hill construction, symmetric plans, and low height-to-width ratios. These are the features that survived the 1934 and 2015 earthquakes.

2.6.2  Basic Principle of Design in Compression

DESIGN VERTICAL LOADING  ≤  DESIGN VERTICAL LOAD RESISTANCE

The left-hand side comes from the known applied loading. The right-hand side is a function of the characteristic compressive strength of the masonry fck, the slenderness ratio and the eccentricity of loading.

IS 1905:1987 uses the working stress method — the actual stress produced by the loads must stay within a permissible limit:

fc  ≤  fper       where fc = actual stress generated, and fper = allowable stress, taken as the limiting strength divided by the factor of safety.

What the permissible compressive stress depends on

  1. Type and strength of the masonry units
  2. Strength (grade) of the mortar
  3. Slenderness ratio
  4. Eccentricity of loading
  5. Shape and size of the units
  6. Cross-sectional area of the masonry
Permissible compressive stress:

fper  =  fb × ks × ka × kp

fb  = basic compressive stress (IS 1905 Table 8), from the unit crushing strength and the mortar type
ks = stress reduction factor (Table 9) — for slenderness ratio and eccentricity
ka = area reduction factor — for a small cross-section
kp = shape modification factor (Table 10) — for the height/width ratio of the unit

2.6.3  Behaviour under Axial and Eccentric Load

Slenderness ratio, SR = heff / teff Failure stress SR = 6 CRUSHING of the material kₛ = 1.0 BUCKLING lateral instability governs kₛ < 1.0, falls with SR 7–24 N/mm² limiting SR (e.g. 27)
Fig. 2.16 Failure stress against slenderness ratio. Up to SR = 6 the member crushes and the full basic compressive stress may be used; beyond it buckling progressively takes over and the stress reduction factor ks cuts the permissible stress down.

2.6.4  Effective Height, Effective Length and Effective Thickness

(a) Effective height heff

The effective height relates to the degree of restraint imposed by the floors and beams that frame into the wall or column. If the ends of a strut were free, pinned or fully fixed the effective height could be computed from Euler buckling theory; IS 1905 tabulates practical values instead. Typical values are:

Support conditionEffective height
Wall laterally supported at top and bottom (RC slab bearing on the full thickness)0.75 H
Wall with partial restraint at top and bottom (timber floor / slab on part thickness)H
Wall laterally supported at bottom only (free at top — parapet, free-standing)1.5 H to 2 H
Column, restrained in both directionsH, or 0.75 H if fully restrained — per Table 5 of IS 1905

Openings in walls. When openings occur such that the masonry between them acts as a pier/column:

Restraint at topDirection perpendicular to the plane of the wallDirection parallel to the plane of the wall
Full restraintheff = 0.75 H + 0.25 H1, where H is the distance between supports and H1 is the height of the taller openingheff = H (the distance between the supports)
Partial restraintheff = H when the height of neither opening exceeds 0.5 H; 2 H when the height of any opening exceeds 0.5 Hheff = 2 H

(b) Effective length leff

The effective length depends on the end conditions along the length of the wall. The four conditions that occur, in various combinations, are:

Various combinations of these determine the effective length; the coefficients are given in Table 4 of IS 1905 (typically 0.8 L for a wall continuous or supported at both ends, 1.0 L for one end supported, 1.5–2.0 L where one end is free).

(c) Effective thickness teff

CaseEffective thickness
Single-leaf solid wall or columnThe actual thickness
Solid wall bonded into piers, buttresses or cross wallsteff = stiffening coefficient × tw (Table 6 of IS 1905). Applies only when the slenderness ratio is based on the effective height; no modification is made when SR is based on the effective length.
Cavity wallTwo-thirds of the sum of the two leaf thicknesses, or the thickness of the thicker leaf, whichever is greater

Table 6 — Stiffening coefficients for walls stiffened by piers, buttresses or cross walls

Sp / WpStiffening coefficient for tp / tw =
123 or more
61.01.42.0
81.01.31.7
101.01.21.4
151.01.11.2
20 or more1.01.01.0

where Sp = centre-to-centre spacing of the pier or cross wall; tp = thickness of the pier; tw = actual thickness of the wall proper; Wp = width of the pier in the direction of the wall, or the actual thickness of the cross wall. Linear interpolation is permitted, extrapolation is not. If the thickness of a cross wall acting as a pier is not given, take tp = 3 tw. Strength is increased by providing piers, buttresses and cross walls, and this stiffening effect is what the coefficient represents.

2.6.5  Slenderness Ratio (SR) 2075 Chaitra, Q3(i)2080 Bhadra, Q2b

SR  =  effective height heffeffective thickness teff   or   effective length leffeffective thickness teff   — whichever is LESS

(For a column, SR is based on the effective height and the corresponding effective thickness in each direction, and the larger of the two governs.)

Influence of slenderness ratio on the strength of a wall

Limiting (maximum permissible) slenderness ratio

Type of wallNumber of storeysMax. SR
Load-bearing walls in cement or cement–lime mortar of type H1, H2, M1 or M2One or two storeys27
Three or more storeys27
Load-bearing walls in lime mortar of type M2 or L1One or two storeys20
Three or more storeys13
Non-load-bearing wallsPanel and curtain walls30
Free-standing walls and parapets10

2.6.6  Eccentricity of Loading

Equivalent eccentricity. When a wall or column carries both an axial load and an eccentric load, the two are replaced by a single equivalent vertical force acting at a statically equivalent eccentricity:

W = W1 + W2      ē = W2 · eW1 + W2      eccentricity ratio = ētw

W1 = axial load, W2 = eccentric load acting at a distance e from the centre line, tw = thickness of the wall.

Effect of eccentricity on the allowable stress (IS 1905, clause 5.4.1.4)

EccentricityTreatment
e ≤ t/24Ignore the stress due to eccentricity — calculate and check the axial stress only.
t/24 < e ≤ t/6The resulting combined axial and bending stress may be allowed to exceed the permissible stress by not more than 25%.
e > t/6Tension occurs on the section. Ignore the part of the thickness in tension; the compressive stress on the extreme fibre is then fc = 2P3 · L · (t/2 − e) (P = vertical load). This stress may again exceed the code value by not more than 25%.

Note also that where the eccentricity ratio lies between 1/3 and 1/2 of the thickness, the stress reduction factor varies linearly between unity and 0.20 for slenderness ratios of 6 and 20 respectively.

2.6.7  The Three Modification Factors 2075 Chaitra2076 Chaitra

(a) Basic compressive stress fb — IS 1905 Table 8

The values in Table 8 take into account the crushing strength of the masonry unit and the grade of mortar. They are valid for SR not exceeding 6, zero eccentricity, and a unit height-to-width ratio (as laid) of 0.75 or less. Alternatively the basic compressive stress may be based on a prism test (Appendix B of the code) on masonry made from the units and mortar actually to be used on the job.

IS 1905 Table 8 giving basic compressive stresses in N per square mm for masonry with different mortar types H1 to L2 and unit crushing strengths from 3.5 to 40 N per square mm
Fig. 2.17 IS 1905:1987, Table 8 — Basic compressive stresses for masonry members. Read down the mortar-type row and across to the column for the unit crushing strength. Source: IS 1905:1987. (Scan artefact: the first three values in the 3.5 N/mm² column print as “8·35” but are 0.35.)

A compact extract of the most-used part of the table:

Mortar type3.55.07.51012.51517.520
H10.350.500.751.001.161.311.451.59
H20.350.500.740.961.091.191.301.41
M10.350.500.740.961.061.131.201.27
M20.350.440.590.810.941.031.101.17
M30.250.410.560.750.870.951.021.10
L10.250.360.530.670.760.830.900.97
L20.250.310.420.530.580.610.650.69

Basic compressive stress fb (N/mm²) — column headings are the unit crushing strength in N/mm². Always confirm against the code in the exam hall; the full table runs to 40 N/mm².

(b) Stress reduction factor ks — IS 1905 Table 9 2076 Chaitra, Q4b(i)

The stress reduction factor ks takes into account both the slenderness ratio of the element and the eccentricity of loading. It reduces the basic compressive stress to allow for the loss of capacity caused by buckling and by the bending induced by eccentric load.

ks = 1.00 for SR ≤ 6 with e = 0, and falls to about 0.43 at SR = 27 for axial load, and much lower still for large eccentricity.
IS 1905 Table 9 giving the stress reduction factor for slenderness ratios from 6 to 27 and eccentricity ratios of 0, 1/24, 1/12, 1/6, 1/4 and 1/3
Fig. 2.18 IS 1905:1987, Table 9 — Stress reduction factor ks for slenderness ratio and eccentricity. Linear interpolation between values is permitted. Source: IS 1905:1987. (At SR = 8, e/t = 1/24 the printed value is a scan defect — read it as 0.95.)

(c) Area reduction factor ka — IS 1905 clause 5.4.1.2

This factor takes into account the smallness of the sectional area of the element. It is applicable only when the sectional area is less than 0.2 m²:

ka = 0.7 + 1.5 A     (A = area of section in m²)

For A ≥ 0.2 m², ka = 1.0 — check: 0.7 + 1.5×0.2 = 1.0. ✓

Reason: a small section has little redundancy, so a single weak brick or badly filled joint has a proportionately larger effect on the capacity.

(d) Shape modification factor kp — IS 1905 Table 10 2075 Chaitra, Q3(ii)

The shape modification factor kp takes into account the shape of the unit — its height to width ratio as laid. It applies only to units of crushing strength up to 15 N/mm².
Height to width ratio of the unit (as laid)kp for units of crushing strength (N/mm²)
5.07.510.015.0
Up to 0.751.01.01.01.0
1.01.21.11.11.0
1.51.51.31.21.1
2.0 to 4.01.81.51.31.2

Linear interpolation between values is permissible.

IS 1905 Table 10 giving shape modification factors for masonry units other than common bricks, for height to width ratios up to 0.75, 1.0, 1.5 and 2.0 to 4.0
Fig. 2.19 IS 1905:1987, Table 10 — Shape modification factor kp for masonry units other than common bricks.Source: IS 1905:1987.

Influence of the shape modification factor on the strength of a wall

2.6.8  Design Procedure for a Wall under Uniformly Distributed Axial Load

Design steps (memorise this sequence — every wall numerical follows it)
  1. Select a trial wall thickness, based on available unit dimensions, the masonry strength required, self-weight considerations, and general requirements (security, temperature, humidity).
  2. Calculate the total load per unit length of wall. Load combinations to consider: DL + LL; DL + appropriate LL + seismic load; DL + appropriate LL + wind load; DL + seismic load.
  3. Calculate the effective height heff and effective length leff.
  4. Calculate the effective thickness teff (apply the stiffening coefficient if the wall is stiffened by piers, buttresses or cross walls).
  5. Calculate the slenderness ratio SR = lesser of heff/teff and leff/teff. Check it against the limiting SR.
  6. Calculate the actual compressive stress σac = P / Ae, where Ae is the effective area per unit length of wall.
  7. Compute the eccentricity e and the eccentricity ratio e/t.
  8. Read the stress reduction factor ks from Table 9 using SR and e/t (e = 0 for a purely axial case).
  9. Select the unit and mortar if not given, and read the basic compressive stress fb from Table 8.
  10. Compute the area reduction factor ka and the shape modification factor kp.
  11. Compute the permissible stress fper = fb ks ka kp.
  12. Apply the design criterion: if σac ≤ fper the wall is SAFE; otherwise increase the thickness, or the unit or mortar strength, and repeat.

2.6.9  Design Criteria for Walls Subjected to Transverse Loading 2076 Chaitra, Q2a

A wall carrying wind or out-of-plane seismic pressure in addition to vertical load must satisfy the following:

  1. Convert the transverse load into an equivalent eccentricity. The lateral pressure produces a moment M; combined with the vertical load W this is expressed as W acting at e = M/W, and the wall is then treated exactly as an eccentrically loaded wall (§2.6.6).
  2. Establish the span direction. A wall supported top and bottom spans vertically; a wall supported by cross walls at its ends spans horizontally; a wall supported on all four sides develops two-way bending. The critical bending moment follows from the support condition.
  3. Check the flexural tensile stress against the very low permissible value. Since masonry has almost no tensile strength, the usual criterion is that the resultant must remain within the middle third, i.e. no tension develops: e ≤ t/6.
  4. Take advantage of the precompression. The vertical dead load produces a compressive stress that must first be overcome before tension can occur; this is why an upper-storey wall with little load on it is far more vulnerable out-of-plane than a heavily loaded ground-floor wall.
  5. Check the combined stress: σ = W/A ± M/Z must be within the permissible compressive stress (with the 25% increase allowed for eccentric/lateral load where applicable), and the tensile side must not exceed the permissible flexural tension.
  6. Check stability and the slenderness limit — free-standing walls and parapets have a limiting SR of only 10.
  7. Provide positive anchorage to the roof/floor with metal anchors so the assumed support condition actually exists, and provide bands and cross walls to reduce the span.

2.7  Emerging Materials and Technologies in Masonry Structures

Material / technologyDescription and benefit
Fly-ash bricksFly ash + lime + gypsum, cured without firing. Uses an industrial waste, saves topsoil and fuel, gives accurate dimensions and higher strength than kiln brick.
AAC blocks (autoclaved aerated concrete)Very light (about one-third the density of brick masonry), good thermal insulation and fire rating; large units mean fast construction and, critically for seismic design, much lower mass and hence lower inertia force.
Compressed stabilised earth blocks (CSEB) and interlocking blocksSoil stabilised with 5–8% cement and machine-pressed. Very low embodied energy; interlocking versions need little or no mortar, tolerate unskilled labour and allow vertical reinforcement through aligned holes. Increasingly used in post-2015 reconstruction in Nepal.
Hollow concrete blocks with reinforced coresVertical bars and grout in the cores turn the wall into genuine reinforced masonry with real ductility.
Confined masonry systemsNow codified worldwide as the recommended low-rise system for seismic regions (see §2.4.2).
Prestressed / post-tensioned masonryVertical tendons add precompression, greatly increasing the out-of-plane and in-plane capacity and giving self-centring behaviour. Used for retaining walls, tanks and footbridges.
Bed-joint reinforcement (ladder/truss mesh, polymer geogrid)Enhances the capacity of walls to resist lateral loading and controls shrinkage cracking, with almost no change in construction method.
Thin-joint / adhesive mortar systems2–3 mm polymer-modified joints with precision units; thinner joints give higher masonry strength (§2.3.4) and faster laying.
FRP, ferrocement and textile-reinforced mortar overlaysCarbon/glass/basalt fabric bonded to the wall face, or a wire-mesh and cement overlay (jacketing) — the leading retrofitting technologies (Chapter 6).
Rat-trap bond and cavity constructionUses 25–35% fewer bricks with better insulation — a low-technology but genuinely economical innovation.
Geopolymer and low-carbon mortars, 3D-printed masonry, robotic bricklayingEmerging research directions aimed at cutting embodied carbon and improving quality control — the single biggest weakness of traditional masonry.

Quick Revision — Facts and Formulae to Memorise

  • Permissible stress: fper = fb × ks × ka × kp.
  • SR = lesser of heff/teff and leff/teff. ks = 1.0 for SR ≤ 6, e = 0.
  • ka = 0.7 + 1.5 A, only when A < 0.2 m².
  • kp from height/width ratio as laid; only for units up to 15 N/mm²; max 1.8.
  • heff = 0.75 H (full restraint), H (partial), 1.5–2 H (free at top). Pier between openings, full restraint: 0.75 H + 0.25 H1.
  • teff = stiffening coefficient × tw — but only when SR is based on effective height, never on effective length. Cavity wall: 2/3 Σt or the thicker leaf, whichever is greater.
  • Limiting SR: 27 (cement mortar load bearing), 20 / 13 (lime mortar, 1–2 / 3+ storeys), 30 (panel & curtain), 10 (free standing & parapet).
  • Eccentricity: ignore if e ≤ t/24; 25% overstress allowed for t/24 < e ≤ t/6; tension develops for e > t/6.
  • Masonry strength ≈ 25–50% of the unit strength. Mortar must be weaker than the unit.
  • Nepal Standard brick: 240 × 115 × 57 mm with a 10 mm joint; water absorption ≤ 15%.
  • Mortar grades: H1 (1:0–0.25:3, 10 MPa) → L1 (1:0:8, 0.7 MPa). Cement mortar never richer than 1:3.
  • Shear: fs = 0.1 + fd/6 ≤ 0.5 N/mm². Em ≈ 550–1100 fm.
  • Hollow unit: net area < 75% of gross; solid unit: ≥ 75%.
  • Confined masonry = wall first, tie-columns cast after. RC frame + infill = frame first, wall after.

Chapter Summary

Masonry is a composite of stiff, strong units bedded in a softer, weaker mortar. It has been used for at least 10,000 years, first entirely by empirical rules of thumb and only in the last few decades by structural calculation. Its nature is composite, heterogeneous, anisotropic, brittle, heavy and extremely sensitive to workmanship; it is strong in compression but almost useless in tension, so it is used for walls, columns, arches and domes. Its advantages are strength in compression, durability, low-cost local materials, fire and thermal performance and long life; its disadvantages are its negligible tensile strength, weight, brittleness and vulnerability to frost, efflorescence and earthquakes.

The units may be burnt clay brick, stone, concrete block, adobe or compressed earth; the Nepal Standard brick is 240×115×57 mm with water absorption not exceeding 15%. Mortars may be cement, lime, cement–lime or mud, graded H1 to L2, and are matched to the unit strength. The strength of masonry is governed by the unit–mortar interaction: the soft mortar tries to expand laterally, is restrained, and puts the unit into lateral tension, so the prism splits vertically through the units at only 25–50% of the unit strength. The strength therefore depends on unit strength and shape, mortar strength and workability, joint thickness, slenderness, eccentricity, sectional area, bond and workmanship.

Structurally, masonry buildings are classified as load-bearing (walls carry everything), confined (walls built first and then confined by RC tie-columns and tie-beams) or infill (masonry panels built into an already-cast RC frame). Walls are classified by function, construction and structural role. Lateral load is resisted by in-plane walls, carried to them by the floor and roof diaphragms, with the out-of-plane walls being the weak link; piers and spandrels govern the behaviour of perforated walls, arches carry load in pure compression at the price of a horizontal thrust, and bands, vertical reinforcement and toothed joints provide the box action that holds the building together. Finally, IS 1905:1987 designs walls by working stress: the permissible compressive stress fper = fb ks ka kp, where the slenderness ratio and eccentricity enter through ks, the smallness of the section through ka = 0.7 + 1.5A, and the height-to-width ratio of the unit through kp.

All Past Exam Questions from this Chapter

CHAPTER 2 — COMPLETE LIST (CE 72502 / ENCE 367)

  1. What are the physical properties of bricks? [4] (2081 Bhadra, Q3a) → §2.3.1
  2. Describe the nature of the masonry structure. [4] (2081 Bhadra, Q4a) → §2.2.2
  3. Define properties and strength of brick masonry, affecting factors and relation of unit and mortar on strength of masonry. [8] (2080 Bhadra, Q2a) → §2.3.1, §2.3.4, §2.3.5
  4. Calculate the effective height, effective length, effective thickness and slenderness ratio of walls A, C, G and P. [12] (2080 Bhadra, Q2b) → §2.6.4, §2.6.5
  5. Explain load-bearing masonry walls, infill masonry, and confined masonry. [8] (2079 Bhadra, Q2a) → §2.4.2
  6. Define masonry structure type based on materials with its advantages and disadvantages. [6] (2078 Bhadra, Q2a) → §2.4.1, §2.2.4
  7. Describe affecting factors and relation between unit and mortar on strength of brick masonry. [6] (2078 Bhadra, Q2b) → §2.3.4, §2.3.5
  8. State and explain briefly the factors affecting the compressive strength of brick masonry. [8] (2076 Chaitra, Q1a) → §2.3.5
  9. Explain the design criteria of walls subjected to transverse loading. [8] (2076 Chaitra, Q2a) → §2.6.9
  10. Explain the following applied to masonry structures: (i) Stress reduction factor (ii) Confined masonry. [4×2] (2076 Chaitra, Q4b) → §2.6.7(b), §2.4.2
  11. Explain the following and state the influence of it on strength of the wall: (i) Slenderness ratio (ii) Shape modification factor. [12] (2075 Chaitra, Q3) → §2.6.5, §2.6.7(d)

In addition, every wall, pier and column design numerical in the paper — 2075 Q4 and Q5, 2076 Q1b, Q2b, Q3b, 2078 Q3 to Q6, 2079 Q3b and Q4b, 2080 Q3a and Q3b, 2081 Q3b and Q4b — is solved using the design procedure of §2.6.8 and the four factors of §2.6.7. Work through the 12-step sequence until it is automatic.